Advertisement

4.4 Power supply and power cable

Requirements for the power supply:
Power (30kW)
2 power modules
3 power modules
4 power modules
5 power modules
Power (40kW)
2 power modules
3 power modules
4 power modules
5 power modules
Cable type: 3P+N+PE, shielded cables are optional if required by local law;
The optional cable shielding must be attached to the PE Rail at both ends of the cable;
The diameter of the cable conductor must be determined by your contractor /
electrician.
Here is the suggestion for the cable dimension of all types C6EU
Power Module (30kW)
2 power modules
3 power modules
4 power modules
5 power modules
Power Module (40kW)
2 power modules
3 power modules
4 power modules
5 power modules
Table 4.4.2 Suggestion for the cable dimension of all types C6EU (cable length within 40m)
Copyright | C6EU SERIES Installation and Operation Manual, Version 1.6
Rated voltage
400V±10%, AC
400V±10%, AC
400V±10%, AC
400V±10%, AC
Rated voltage
400V±10%, AC
400V±10%, AC
400V±10%, AC
400V±10%, AC
Table 4.4.1 Requirements for the power supply
Cable dimension
4x35 mm
2
1x16 mm
2
4x50 mm
2
1x25 mm
2
4x95 mm
2
1x50 mm
2
4x150 mm
2
1x95 mm
2
Cable dimension
4x50 mm
2
1x25 mm
2
4x95 mm
2
1x50 mm
2
4x150 mm
2
1x95 mm
2
4x185 mm
2
1x95 mm
2
Rated current
92A
140A
185A
230A
Rated current
120A
185A
245A
304A
Cable gland (diameter)
M50 (32 - 38 mm)
M72 (52 - 60 mm)
M72 (52 - 60 mm)
M72 (52 - 60 mm)
Cable gland (diameter)
M72 (52 - 60 mm)
M72 (52 - 60 mm)
M72 (52 - 60 mm)
M90 (62 - 70 mm)
Frequency
50Hz
50Hz
50Hz
50Hz
Frequency
50Hz
50Hz
50Hz
50Hz
(cable length within
40m):
Circuit breaker inside
4P 125A with RCD Type A
4P 180A with RCD Type A
4P 250A with RCD Type A
4P 350A with RCD Type A
Circuit breaker inside
4P 160A with RCD Type A
4P 250A with RCD Type A
4P 350A with RCD Type A
4P 400A with RCD Type A
21