We do assure you that all persons are regarded without discrim- ination and on an equal basis. All rights to this documentation are reserved by Pilz GmbH & Co. KG. Copies may be made for the user's internal purposes. Suggestions and comments for improving this documenta- tion will be gratefully received.
..........................Installing the base module ......................Inserting and removing an electronic module ................5.3.1 Inserting an electronic module....................5.3.2 Removing an electronic module ....................5.3.3 Changing an electronic module during operation ..............Operating Manual PSSu E S 2AO I(-T) 21435-EN-04...
Page 4
Connecting the module......................Operation ..........................Messages ..........................Display elements ........................7.2.1 Display elements for module diagnostics ................. 7.2.2 Display elements for output status.................... Technical details ........................Order reference ........................Product ............................. Accessories ..........................Operating Manual PSSu E S 2AO I(-T) 21435-EN-04...
Introduction Validity of documentation This documentation is valid for the products PSSu E S 2AO I and PSSu E S 2AO I-T. It is valid until new documentation is published. This operating manual explains the function and operation, describes the installation and provides guidelines on how to connect the product.
It also highlights areas within the text that are of particular import- ance. INFORMATION This gives advice on applications and provides information on special fea- tures. Operating Manual PSSu E S 2AO I(-T) 21435-EN-04...
Resolution: 12 Bit LEDs for: – Operating status per output – Module error For standard applications in system environment A and B T-type: PSSu E S 2AO I-T: for increased environmental requirements Operating Manual PSSu E S 2AO I(-T) 21435-EN-04...
– Serial number – Hardware version number – 2D code 3: Labelling strip for the terminal configuration on the base module 4: Name of electronic module 5: Connection level 1 6: Connection level 2 Operating Manual PSSu E S 2AO I(-T) 21435-EN-04...
Page 9
10: Round connection holes (connection levels 1, 2, 3 and 4) for connecting the signal lines 11: Mounting slot for colour marker to label the connection level (connection levels 1, 2, 3 and 4) Operating Manual PSSu E S 2AO I(-T) 21435-EN-04...
PAS4000 from Version 1.0.0 – We recommend that you always use the latest version (download from www.pilz.com). The PSSu E S 2AO I module may be used in conjunction with the following base modules: PSSu BP 1/8 S PSSu BP 1/8 C...
Safety The module PSSu E S 2AO I-T may be used in conjunction with the following base mod- ules: PSSu BP 1/8 S-T PSSu BP 1/8 C-T PSSu BP 1/12 S-T PSSu BP 1/12 C-T PSSu BP-C 1/8 S-T PSSu BP-C 1/8 C-T...
All the configuration data is stored in the head module and is assigned to the output module on restart. This way the configuration data is retained even if you change the output mod- ule. Schematic representation of signal processing: User Manufact. scaling scaling Data module format Operating Manual PSSu E S 2AO I(-T) | 12 21435-EN-04...
Via the head module's USB port with PAS4000. 4.3.1 Current range You can configure the following current ranges per module: 0 ... 20 mA single-pole, referenced to earth (single-ended) 4 ... 20 mA single-pole, referenced to earth (single-ended) Operating Manual PSSu E S 2AO I(-T) | 13 21435-EN-04...
Binary digital value Hexadecimal digital rent value 4 mA 0000 0000 0000 0000 0000 12 mA 16 384 0100 0000 0000 0000 4000 20 mA 32 767 0111 1111 1111 1111 7FFF Operating Manual PSSu E S 2AO I(-T) | 14 21435-EN-04...
Scaling is a multi-stage process to adapt the values to the DA converter. The straight path in the diagram indicates the default configuration. Input formats Raw value output? Hardware calibration Manuf. scaling active? Manufacturer scaling User scaling active? User scaling raw value Operating Manual PSSu E S 2AO I(-T) | 15 21435-EN-04...
Each channel is calibrated ex-works in order to correct component dispersion and other in- fluences. The range is divided so that zero is assigned the value 0 and the end point is assigned the value 4095 (0FFF Operating Manual PSSu E S 2AO I(-T) | 16 21435-EN-04...
With the given amplification factor, gain (a ) is calculated as follows: Gain (a ) = Amplification factor * 256 Amplification by 5 % is therefore: 1.05 * 256 = 269 Operating Manual PSSu E S 2AO I(-T) | 17 21435-EN-04...
). Manufacturer scaling should not be changed. All numbers are decimals. Solution: User scaling y = (a / 256 * x) + b and manufacturer scaling y = (a / 256 * x) + b Operating Manual PSSu E S 2AO I(-T) | 18 21435-EN-04...
The relationship between the switch-on value and the actual current at the output is de- pendent on the scaling. The module sets the current, which corresponds to the switch-on voltage after scaling. Please refer to the "Scaling" section in this manual. Operating Manual PSSu E S 2AO I(-T) | 19 21435-EN-04...
Each output channel occupies 16 consecutive bit addresses for the output data. Configuration Standard bus system ST-PII ST-PIO None - - - 32 Bit Bit sequence in the PIO: Input Assignment Output O0 Output O1 Operating Manual PSSu E S 2AO I(-T) | 20 21435-EN-04...
PSSu assignment in system environment B Data access is via pre-defined I/O data types: I/O data name I/O data type I/O data element Meaning O0(11), O1(21) ST_O_AO Data: WORD Output data O0, O1 Operating Manual PSSu E S 2AO I(-T) | 21 21435-EN-04...
5.1.1 Dimensions Base modules with four connection levels: 12,6 mm 8,1 mm 52,1 mm (0.496") (0.319") (2.051") 12,6 mm 72,6 mm (0.496") (2.858") Operating Manual PSSu E S 2AO I(-T) | 22 21435-EN-04...
Page 23
Installation Base modules with six connection levels: 12,6 mm 8,1 mm 52,1 mm (0.496") (0.319") (2.051") 12,6 mm 72,6 mm (0.496") (2.858") Operating Manual PSSu E S 2AO I(-T) | 23 21435-EN-04...
Push the base module back [2] until you hear it lock into position. On the mounting rail, slide the base module to the left until you hear the two lateral mounting hooks on the adjacent module lock into position [3]. Schematic representation: Operating Manual PSSu E S 2AO I(-T) | 24 21435-EN-04...
This is how the base module is coded. The mechanics of the electronic modules are designed for 50 plug in/out cycles. Operating Manual PSSu E S 2AO I(-T) | 25 21435-EN-04...
Installation 5.3.1 Inserting an electronic module Procedure: The electronic module must audibly lock into position [1]. Mark the electronic module using the labelling strips [2]. Schematic representation: Operating Manual PSSu E S 2AO I(-T) | 26 21435-EN-04...
– The substitute values are used for the modules' FS outputs, with Valid Bits = FALSE. CAUTION! Sparking can cause interference and errors! Only change the module when the load is switched off! Operating Manual PSSu E S 2AO I(-T) | 27 21435-EN-04...
The terminal configuration as stated in the technical documentation applies for all other base modules. 6.1.1 Mechanical connection of the base modules Procedure: Use a flat blade screwdriver (DIN 5264-A)! DIN 5264-A Strip the wire back 8 mm. Operating Manual PSSu E S 2AO I(-T) | 28 21435-EN-04...
Page 29
– Pull out the screwdriver [6]. – Check that the cable is firmly seated. Please note: The minimum cable cross section for field connection terminals on the base modules is 0.14 mm (AWG26). Operating Manual PSSu E S 2AO I(-T) | 29 21435-EN-04...
PSSu BP 1/8 C PSSu BP 1/8 C-T 12-22: 0 V analogue (12-22 linked within the base module) 13-23: Shield connection (13-23 linked within the base module) 14: Not connected 24: Not connected Operating Manual PSSu E S 2AO I(-T) | 30 21435-EN-04...
Page 31
PSSu BP-C 1/8 C-T 12-22: 0 V analogue (12-22 linked within the base module) 13-23: C-rail supply, shield connection (13-23 linked within the base module) 14: Not connected 24: Not connected Operating Manual PSSu E S 2AO I(-T) | 31 21435-EN-04...
Wiring Connecting the module Output circuit Without C-rail With C-rail current range 0 ... 20 mA current range 4 ... 20 mA single-pole, referenced to earth Operating Manual PSSu E S 2AO I(-T) | 32 21435-EN-04...
Timeout error on the output No data has been received for the Check ST communication or con- output from the module bus for figuration. longer than 50 ms. Operating Manual PSSu E S 2AO I(-T) | 33 21435-EN-04...
Designa- Colour Status Signal Output Ter- tion minal - - - No signal O0 (Output detected green Signal detected - - - No signal O1 (Output detected green Signal detected Operating Manual PSSu E S 2AO I(-T) | 34 21435-EN-04...
0,15 % 0,15 % Output variable error at 25 ℃ 0,3 % 0,3 % Max. output variable error for EMC measurements at 25 °C Temperature coefficient 0,02 %/K 0,02 %/K Operating Manual PSSu E S 2AO I(-T) | 35 21435-EN-04...
Page 36
EN 60068-2-27 Number of shocks Acceleration Duration 11 ms 11 ms In accordance with the standard EN 60068-2-27 EN 60068-2-27 Number of shocks 1000 1000 Acceleration Duration 16 ms 16 ms Operating Manual PSSu E S 2AO I(-T) | 36 21435-EN-04...
Page 37
12,6 mm Depth 60,2 mm 60,2 mm Weight 36 g 38 g Mechanical coding Type Colour Dark grey Dark grey Where standards are undated, the 2005-04 latest editions shall apply. Operating Manual PSSu E S 2AO I(-T) | 37 21435-EN-04...
Base module with C-rail and screw terminals, T-type 314620 PSSu BP-C 1/12 C Base module with C-rail and cage clamp terminals 312621 PSSu BP-C 1/12 C-T Base module with C-rail and cage clamp terminals, T-type 314621 Operating Manual PSSu E S 2AO I(-T) | 38 21435-EN-04...
Page 39
We are represented internationally. Please refer to our homepage www.pilz.com for further details or contact our headquarters. Headquarters: Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: info@pilz.com, Internet: www.pilz.com...