Pilz PSSu E S 4DI Operating Manual
Pilz PSSu E S 4DI Operating Manual

Pilz PSSu E S 4DI Operating Manual

Decentralised system pssuniversal i/o

Advertisement

Quick Links

PSSu E S 4DI(-T)
}
Decentralised system PSSuniversal I/O
Operating Manual-21340-EN-08

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the PSSu E S 4DI and is the answer not in the manual?

Questions and answers

Summary of Contents for Pilz PSSu E S 4DI

  • Page 1 PSSu E S 4DI(-T) Decentralised system PSSuniversal I/O Operating Manual-21340-EN-08...
  • Page 2 Preface This document is a translation of the original document. All rights to this documentation are reserved by Pilz GmbH & Co. KG. Copies may be made for internal purposes. Suggestions and comments for improving this documentation will be gratefully received.
  • Page 3: Table Of Contents

    Removing an electronic module 5.3.3 Changing an electronic module during operation Section 6 Wiring General wiring guidelines 6.1.1 Mechanical connection of the base modules Terminal configuration Connecting the module Section 7 Operation Messages Display elements Operating Manual PSSu E S 4DI(-T) 21340-EN-08...
  • Page 4 Contents 7.2.1 Display elements for module diagnostics 7.2.2 Display elements for input status Section 8 Technical details Section 9 Order reference Product Accessories Operating Manual PSSu E S 4DI(-T) 21340-EN-08...
  • Page 5: Introduction

    Introduction Validity of documentation This documentation is valid for the products PSSu E S 4DI and PSSu E S 4DI-T. It is valid until new documentation is published. This operating manual explains the function and operation, describes the installation and provides guidelines on how to connect the product.
  • Page 6: Definition Of Symbols

    It also highlights areas within the text that are of particular import- ance. INFORMATION This gives advice on applications and provides information on special fea- tures. Operating Manual PSSu E S 4DI(-T) 21340-EN-08...
  • Page 7: Overview

    The product has the following features: 4 Digital inputs LEDs for: – Switch status of each input – Module error For standard applications in system environment A and B T-type: PSSu E S 4DI-T: for increased environmental requirements Operating Manual PSSu E S 4DI(-T) 21340-EN-08...
  • Page 8: Front View

    – Serial number – Hardware version number – 2D code 3: Labelling strip for the terminal configuration on the base module 4: Status LEDs 5: Name of electronic module 6: Connection level 1 Operating Manual PSSu E S 4DI(-T) 21340-EN-08...
  • Page 9 11: Round connection holes (connection levels 1, 2, 3 and 4) for connecting the signal lines 12: Mounting slot for colour marker to label the connection level (connection levels 1, 2, 3 and 4) Operating Manual PSSu E S 4DI(-T) 21340-EN-08...
  • Page 10: Safety

    The module may be used for standard applications in system environment A and B. The modules PSSu E S 4DI and PSSu E S 4DI-T may be used as a safety components in accordance with the Lifts Directive 95/16/EC in accordance with the requirements of EN 81-1/2:1998+A3:2009, EN 81-20:2015, EN 81-50:2015, EN 81-22:2014 and...
  • Page 11: Safety Regulations

    Safety The module PSSu E S 4DI-T may be used in conjunction with the following base modules: PSSu BP 1/8 S-T PSSu BP 1/8 C-T PSSu BP-C 1/8 S-T PSSu BP-C 1/8 C-T PSSu BP 1/12 S-T PSSu BP 1/12 C-T...
  • Page 12: Function Description

    When the PSSu E F PS1(-T) or PSSu E F PS2(-T)(-R) is used to supply the system, the module supply is buffered for 20 ms if the supply voltage is interrupted. The module detects the following errors: Start-up error Configuration error ST communication error Bus termination error Operating Manual PSSu E S 4DI(-T) 21340-EN-08...
  • Page 13: Reaction Times

    PSS WIN-PRO system software, but ST modules can be selected and displayed. The ST process image can be optimised by combining adjacent bits of the same type into bytes. Further information on configuration is available in the PSSuniversal Configurator's online help. Operating Manual PSSu E S 4DI(-T) 21340-EN-08...
  • Page 14: Addresses In The Process Image

    PSSu assignment in system environment B Data access is via pre-defined I/O data types: I/O data name I/O data type I/O data element Meaning I0(11), I1(21), I2(14), I3(24) ST_I_DI Data: BOOL Input data I0 ... I3 Operating Manual PSSu E S 4DI(-T) 21340-EN-08...
  • Page 15: Installation

    5.1.1 Dimensions Base modules with four connection levels: 12,6 mm 8,1 mm 52,1 mm (0.496") (0.319") (2.051") 12,6 mm 72,6 mm (0.496") (2.858") Operating Manual PSSu E S 4DI(-T) 21340-EN-08...
  • Page 16: Installing The Base Module

    Push the base module back [2] until you hear it lock into position. On the mounting rail, slide the base module to the left until you hear the two lateral mounting hooks on the adjacent module lock into position [3]. Operating Manual PSSu E S 4DI(-T) 21340-EN-08...
  • Page 17: Inserting And Removing An Electronic Module

    This is how the base module is coded. The mechanics of the electronic modules are designed for 50 plug in/out cycles. Operating Manual PSSu E S 4DI(-T) 21340-EN-08...
  • Page 18: Inserting An Electronic Module

    Installation 5.3.1 Inserting an electronic module Procedure: The electronic module must audibly lock into position [1]. Mark the electronic module using the labelling strips [2]. Schematic representation: Operating Manual PSSu E S 4DI(-T) 21340-EN-08...
  • Page 19: Removing An Electronic Module

    – The substitute values are used for the modules' FS outputs, with Valid Bits = FALSE. CAUTION! Sparking can cause interference and errors! Only change the module when the load is switched off! Operating Manual PSSu E S 4DI(-T) 21340-EN-08...
  • Page 20: Wiring

    Insert the screwdriver [4] into the square hole [1]. – Insert the stripped cable into the round fixing hole [2], as far as it will go [5]. – Pull out the screwdriver [6]. – Check that the cable is firmly seated. Operating Manual PSSu E S 4DI(-T) 21340-EN-08...
  • Page 21 To crimp the ferrules you can use crimp pliers (crimp form A or C) conforming to EN 60947-1, such as the PZ 1.5 or PZ 6.5 from Weidmüller, for example. – Maximum torque setting: 0.8 Nm Operating Manual PSSu E S 4DI(-T) 21340-EN-08...
  • Page 22: Terminal Configuration

    PSSu BP 1/8 C-T 12-22: +24 V output (periphery supply, 12-22 linked within the base mod- ule) 13-23: +24 V output (periphery supply, 13-23 linked within the base mod- ule) 14: Input I2 24: Input I3 Operating Manual PSSu E S 4DI(-T) 21340-EN-08...
  • Page 23 PSSu BP-C 1/8 C PSSu BP-C 1/8 C-T 12-22: +24 V output (periphery supply, 12-22 linked within the base mod- ule) 13-23: C-rail supply (13-23 linked within the base module) 14: Input I2 24: Input I3 Operating Manual PSSu E S 4DI(-T) 21340-EN-08...
  • Page 24 (13-23-16-26 linked within the base module) 14: Input I2 24: Input I3 15-25: +24 V output (periphery supply, 15-25 linked within the base module) 16-26: C-rail supply (13-23-16-26 linked within the base module) Operating Manual PSSu E S 4DI(-T) 21340-EN-08...
  • Page 25: Connecting The Module

    Connecting the module Input circuit Single-channel input device Single-channel input device Input devices supplied via the peri- phery supply 24 V 24 V 24 V 24 V 24 V 24 V 24 V 24 V Operating Manual PSSu E S 4DI(-T) 21340-EN-08...
  • Page 26: Operation

    Legend LED on LED off 7.2.1 Display elements for module diagnostics The module has an LED for displaying module errors ("Err" LED). Meaning Name Colour Status - - - No error Module error Operating Manual PSSu E S 4DI(-T) 21340-EN-08...
  • Page 27: Display Elements For Input Status

    - - - 0 signal 13 23 (Input 2) 14 24 Green 1 signal - - - 0 signal (Input 3) Green 1 signal - - - 0 signal (Input 4) Green 1 signal Operating Manual PSSu E S 4DI(-T) 21340-EN-08...
  • Page 28: Technical Details

    4 ms Min. processing time of input when signal changes from "1" to "0" 3 ms 3 ms Min. processing time of input when signal changes from "0" to "1" 3 ms 3 ms Operating Manual PSSu E S 4DI(-T) 21340-EN-08...
  • Page 29 In accordance with the standard EN 60068-2-27 EN 60068-2-27 Number of shocks 1000 1000 Acceleration Duration 16 ms 16 ms Airgap creepage In accordance with the standard EN 60664-1 EN 60664-1 Overvoltage category Pollution degree Operating Manual PSSu E S 4DI(-T) 21340-EN-08...
  • Page 30 Width 12,6 mm 12,6 mm Depth 60,2 mm 60,2 mm Weight 31 g 31 g Mechanical coding Type Colour Dark grey Dark grey Where standards are undated, the 2005-04 latest editions shall apply. Operating Manual PSSu E S 4DI(-T) 21340-EN-08...
  • Page 31: Order Reference

    PSSu BP-C1 1/12 S-T Base module with C-rail and screw terminals, T-type 314 622 PSSu BP-C1 1/12 C Base module with C-rail and cage clamp terminals 312 623 PSSu BP-C1 1/12 C- Base module with C-rail and cage clamp terminals, T-type 314 623 Operating Manual PSSu E S 4DI(-T) 21340-EN-08...
  • Page 32 Titelseite Support Technical support is available from Pilz round the clock. Americas Australia Scandinavia Brazil +61 3 95600621 +45 74436332 +55 11 97569-2804 Spain Canada Europe +34 938497433 +1 888-315-PILZ (315-7459) Austria Switzerland Mexico +43 1 7986263-0 +41 62 88979-30...

This manual is also suitable for:

Pssu e s 4di-t

Table of Contents