Page 1
PSSu E S 4DI-D Decentralised system PSSuniversal I/O Operating Manual-1001322-EN-07...
Page 2
We do assure you that all persons are regarded without discrim- ination and on an equal basis. All rights to this documentation are reserved by Pilz GmbH & Co. KG. Copies may be made for the user's internal purposes. Suggestions and comments for improving this documenta- tion will be gratefully received.
Changing an electronic module during operation ..............Wiring ............................General wiring guidelines ......................6.1.1 Mechanical connection of the base modules................Terminal configuration ......................Connecting the module......................Operation ..........................Messages ..........................Display elements ........................Operating Manual PSSu E S 4DI-D 1001322-EN-07...
Page 4
Contents 7.2.1 Display elements for module diagnostics ................. 7.2.2 Display elements for input status....................Technical Details ........................Order reference ........................Product ............................. Accessories ..........................Operating Manual PSSu E S 4DI-D 1001322-EN-07...
Introduction Introduction Validity of documentation This documentation is valid for the product PSSu E S 4DI-D. It is valid until new document- ation is published. This operating manual explains the function and operation, describes the installation and provides guidelines on how to connect the product.
It also highlights areas within the text that are of particular import- ance. INFORMATION This gives advice on applications and provides information on special fea- tures. Operating Manual PSSu E S 4DI-D 1001322-EN-07...
– Module error The module provides advanced diagnostic data. Optional access to the advanced diagnostic data in the process image (system environ- ment A only) For standard applications in system environment A and B Operating Manual PSSu E S 4DI-D 1001322-EN-07...
– 2D code 3: Labelling strip for the terminal configuration on the base module 4: Status LEDs 5: Name of electronic module 6: Connection level 1 7: Connection level 2 8: Connection level 3 Operating Manual PSSu E S 4DI-D 1001322-EN-07...
Page 9
11: Round connection holes (connection levels 1, 2, 3 and 4) for connecting the signal lines 12: Mounting slot for colour marker to label the connection level (connection levels 1, 2, 3 and 4) Operating Manual PSSu E S 4DI-D 1001322-EN-07...
PAS4000 from Version 1.8.0 – We recommend that you always use the latest version (download from www.pilz.com). The PSSu E S 4DI-D module may be used in conjunction with the following base modules: PSSu BP 1/8 S PSSu BP 1/8 C...
In safety-related applications, please comply with the mission time T in the safety-related characteristic data. When decommissioning, please comply with local regulations regarding the disposal of electronic devices (e.g. Electrical and Electronic Equipment Act). Operating Manual PSSu E S 4DI-D | 11 1001322-EN-07...
The supply outputs cannot be controlled via the process image (PIO). The module provides advanced diagnostic data, which is also available in a status byte in the ST-PII (not in system environment B): Output overload/short circuit Excess module temperature Operating Manual PSSu E S 4DI-D | 12 1001322-EN-07...
Temperature error: too hot 4.2.3 Reaction times Information on the reaction times of the inputs can be found in the "PSSuniversal" System Description and the System Description "Automation system PSS 4000". Operating Manual PSSu E S 4DI-D | 13 1001322-EN-07...
No overload on supply output S1 Overload on supply output S1 No overload on supply output S2 Overload on supply output S2 Reserved Reserved Reserved Reserved No temperature error Temperature error: too warm Operating Manual PSSu E S 4DI-D | 14 1001322-EN-07...
I/O data name I/O data type I/O data element Meaning I0(11), I1(21), I2(14), I3(24) ST_I_DI Data: BOOL Input data I0 ... I3 The status byte is not available in the process image. Operating Manual PSSu E S 4DI-D | 15 1001322-EN-07...
5.1.1 Dimensions Base modules with four connection levels: 12,6 mm 8,1 mm 52,1 mm (0.496") (0.319") (2.051") 12,6 mm 72,6 mm (0.496") (2.858") Operating Manual PSSu E S 4DI-D | 16 1001322-EN-07...
Push the base module back [2] until you hear it lock into position. On the mounting rail, slide the base module to the left until you hear the two lateral mounting hooks on the adjacent module lock into position [3]. Operating Manual PSSu E S 4DI-D | 17 1001322-EN-07...
This is how the base module is coded. The mechanics of the electronic modules are designed for 50 plug in/out cycles. Operating Manual PSSu E S 4DI-D | 18 1001322-EN-07...
Installation 5.3.1 Inserting an electronic module Procedure: The electronic module must audibly lock into position [1]. Mark the electronic module using the labelling strips [2]. Schematic representation: Operating Manual PSSu E S 4DI-D | 19 1001322-EN-07...
– The substitute values are used for the modules' FS outputs, with Valid Bits = FALSE. CAUTION! Sparking can cause interference and errors! Only change the module when the load is switched off! Operating Manual PSSu E S 4DI-D | 20 1001322-EN-07...
– Insert the stripped cable into the round fixing hole [2], as far as it will go [5]. – Pull out the screwdriver [6]. – Check that the cable is firmly seated. Operating Manual PSSu E S 4DI-D | 21 1001322-EN-07...
Page 22
– Inputs/outputs on the counter modules: 1.5 mm (AWG16) – Analogue inputs/outputs: 1.5 mm (AWG16) – Communication cables: 1.5 mm (AWG16) – Test pulse outputs: 1.5 mm (AWG16) – Power supply: 2.5 mm (AWG12) – Functional earth: 2.5 mm (AWG12) Operating Manual PSSu E S 4DI-D | 22 1001322-EN-07...
PSSu BP 1/8 C PSSu BP 1/8 C-T 12-22: Supply output S1 (12-22 linked within the base module) 13-23: Supply output S2 (13-23 linked within the base module) 14: Input I2 24: Input I3 Operating Manual PSSu E S 4DI-D | 23 1001322-EN-07...
Page 24
(13-23-16-26 linked within the base module) 14: Input I2 24: Input I3 15-25: Supply output S1 (12-22-15-25 linked within the base module) 16-26: Supply output S2 (13-23-16-26 linked within the base module) Operating Manual PSSu E S 4DI-D | 24 1001322-EN-07...
Page 25
(13-23-16-26 linked within the base module) 14: Input I2 24: Input I3 15-25: Supply output S2 (15-25 linked within the base module) 16-26: C-rail supply (13-23-16-26 linked within the base module) Operating Manual PSSu E S 4DI-D | 25 1001322-EN-07...
"too warm" threshold value, the supply outputs will switch back on. Further information on PSSu error messages is available in the online help for the system software PSSuniversal Configurator or PSSuniversal Startup. Operating Manual PSSu E S 4DI-D | 27 1001322-EN-07...
0 signal 13 23 (Input 2) 14 24 Green 1 signal - - - 0 signal (Input 3) Green 1 signal - - - 0 signal (Input 4) Green 1 signal Operating Manual PSSu E S 4DI-D | 28 1001322-EN-07...
Potential isolation between input and internal module bus voltage Semiconductor outputs Rated voltage 24 V DC Permitted loads inductive, capacitive, resistive Voltage outputs Number of outputs for periphery supply Function of outputs for periphery supply Sensor supply Operating Manual PSSu E S 4DI-D | 29 1001322-EN-07...
Page 30
Airgap creepage In accordance with the standard EN 60664-1, EN 61131-2 Overvoltage category Pollution degree Protection type In accordance with the standard EN 60529 Housing IP20 Mounting area (e.g. control cabinet) IP54 Operating Manual PSSu E S 4DI-D | 30 1001322-EN-07...
Page 31
Front Coding Dimensions Height 76 mm Width 12,6 mm Depth 60,2 mm Weight 31 g Mechanical coding Type Colour Dark grey Where standards are undated, the 2008-03 latest editions shall apply. Operating Manual PSSu E S 4DI-D | 31 1001322-EN-07...
Base module without C-rail with cage clamp terminals 312 619 PSSu BP-C1 1/12 S Base module with C-rail and screw terminals 312 622 PSSu BP-C1 1/12 C Base module with C-rail and cage clamp terminals 312 623 Operating Manual PSSu E S 4DI-D | 32 1001322-EN-07...
Page 33
We are represented internationally. Please refer to our homepage www.pilz.com for further details or contact our headquarters. Headquarters: Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: info@pilz.com, Internet: www.pilz.com...