4 channel two pipes fan coil controller
ZCL-4XFC2P
FEATURES
 Up to four blocks to control 2-pipe fan coil units.
 Manual output operation with push button and LED status
indicator.
 Logical functions included.
 Output timing facilities.
 Total data saving on power failure.
 Size 90 x 60 x 140 mm (8 DIN units).
DIN rail mounting (EN 50022), through pressure.
 No external power supply required other than the bus.
 Integrated KNX BCU.
 Possibility to connect different phases in adjoining outputs.
 Conformity with the CE directives (CE-mark on the right side).
1. Upper outputs
5.Programming/Test button
Programming/test button: short press to set programming mode. If this button is held while plugging the device into the KNX bus, it enters the safe
mode. If this button is held for more than 3 seconds, the device enters the test mode.
Programming/Test LED: programming mode indicator (red). When the device enters into safe mode, it blinks (red) every half second. The manual
mode is indicated by the green color. During the start-up (reset or after KNX bus failure) and if the device is not in safe mode, it starts a blue blinking
sequence.
GENERAL SYSTEM SPECIFICATIONS
CONCEPT
Type of device
Voltage (typical)
Voltage range
KNX
Maximum
Supply
consumption
Bus connection
External power supply
Operation temperature
Storage temperature
Operation humidity
Storage humidity
Complementary characteristics
Protection class
Operation type
Device action type
Electrical stress period
Degree of protection
Installation
Response on KNX bus failure
Response on KNX bus restart
Operation indication
Weight
PCB CTI index
Housing material
(1)
Maximum consumption in the worst case scenario (KNX Fan-In model)
© Zennio Avance y Tecnología S.L.
2. Lower outputs
6.Output control button
DESCRIPTION
Electric operation control device
29VDC SELV
21...31V DC
Voltage
29VDC (typical)
(1)
24VDC
Typical bus connector TP1 for rigid cable 0.80mm Ø
No
from 0ºC to +55ºC
from -20ºC to +70ºC
5 to 95% RH (no condensation)
5 to 95% RH (no condensation)
Class B
II
Continuous operation
Type 1
Long
IP20, clean environment
Independent device to be mounted inside electrical panels with DIN rail (EN 50022)
Data saving and output status change according to programming.
Data recovering and output status change according to programming.
Programming LED indicates programming mode (red) and test mode (green).
Output status LED indicators reflect current output state.
440g
175V
PC FR V0 halogen free
Edition 3
MAXinBOX FANCOIL 4CH2P
6
3
2
Figure 1. MAXinBOX FANCOIL 4CH2P
3.Programming/Test LED
7.Output status LED indicator
mA
7.5
10
Further information
www.zennio.com
Technical Documentation
1
7
5
4
4.KNX connector
mW
217,5
240
Page 1 / 2

Advertisement

loading

Summary of Contents for Zennio MAXinBOX FANCOIL 4CH2P

  • Page 1  No external power supply required other than the bus.  Integrated KNX BCU.  Possibility to connect different phases in adjoining outputs.  Conformity with the CE directives (CE-mark on the right side). Figure 1. MAXinBOX FANCOIL 4CH2P 1. Upper outputs 2. Lower outputs 3.Programming/Test LED 4.KNX connector...