Condenser Modulating Valve Removal - Cornelius 1000 - Series Service Manual

500, 700, 1000, 2000 - series continuous flow icemaker
Hide thumbs Also See for 1000 - Series:
Table of Contents

Advertisement

Continuous Flow Icemaker Service Manual
C
M
ONDENSER
ODULATING
1.
Disconnect power to unit, then shut off water supply to condenser and evacuate refrigerant from
system.
2.
Remove inlet water line from Condenser Modulating Valve. Also remove tube from high side
refrigerant line.
3.
Remove Condenser Modulating Valve and bracket from unit.
4.
Remove valve from bracket.
5.
Replace Condenser Modulating Valve by reversing Steps 2 through 4. Then pull system into
vacuum.
6.
Charge unit with proper amount of refrigeration.
7.
Turn power and water on to unit.
8.
With unit running, adjust modulating valve to proper setting.
9.
Go through a complete system check.
OVERLOAD GUIDE
ELECTRICAL:
High or low voltage. Weak power lines can cause overloads on icemakers restarts.
High running current (2.4amps or above). Check motor circuits and start relay.
Auger delay failed.
ICEMAKER
Mechanical parts worn. Scored evaporator or auger. Worn thrust bearing.
Icemaker not turning off. Failed ice level control.
Over compression. Low water inlet temperature. Restrictions in water line from reservoir.
REFRIGERANT
Contaminated charge or bad compressor.
Low charge or gas leak.
Low suction pressure. Improper expansion valve. Sensing bulb location or insulation
and/or defective expansion valve.
Publication Number: 630460174SER
V
R
ALVE
IMPORTANT
Icemaker runs when
reset but problem has
not been found.
Continue checking for
overload as follows to
guard against future
problems.
EMOVAL
OVERLOAD TRIPPED
Check water level control
and evaporator water tube
for line build-up restrictions.
NO
CAUTION
Clear ice from
evaporator and
auger before
resetting overload.
Reset overload.
Icemaker
Resets but
runs.
motor does
not run.
Short run. Trips
again in 2
Resets but
minutes. Check
motor does
gearmotor circuits.
not run.
Check
gearmotor
circuits.
- 14 -
GEARMOTOR
YES
CLEAN
See Instructions.
Will not
Reset.
Overload
hot try
again.
Will not
reset.
Replace
overload.
© 2004-2005, IMI Cornelius Inc.