Wired Remote Controller Installation/Service Mode

Additional Functions of Your Wired Remote Controller
In some cases, the setting may not possible or it may be not applied though it is set on the unit.
communication will be initialized.
Main
Sub
menu
menu
Wireless remote controller
1
Option setting/checking (1)
Wireless remote controller
2
Option setting/checking (2)
Blade
3
setting/checking
1
4
Setting/checking
Room Temperature
5
compensation
6
Number of connected units
7
Temperature increment/decrement (°C only)
8
operation
0
1
2
2
Function
Cooling/Heating selection
Use of wireless remote controller
MAIN/SUB wired remote
controller
Temperature unit
Temperature sensor selection
Use of average temperature
Use of Auto mode
Temperature display
AC On/Off button function
Lock of Blade1
Lock of Blade2
Lock of Blade3
Lock of Blade4
Use of By-Pass mode
Use of Auto mode
Use of air purification mode
Use of external control
Temperature control reference
Temperature compensation value
Number of indoor units
Select individual Energy saving
operation
Minimum temperature of
outdoor air cooling
Factory option setting
Software code
Software version
Data
Factory
Description
bit
setting
0 – Cooling/Heating,
1
0
1 – Cooling only
2
1
0 – No use, 1 - Use
3
0
0 –MAIN, 1- SUB
4
0
0 – Celcius(°C), 1 – Fahrenheit(°F)
0 – Indoor unit,
1
0
1 – Wired remote controller
2
0
0 – No use, 1 - Use
3
1
0 – No use, 1 - Use
0 – Set temperature,
4
0
1 - Room temperature
5
0
1 – Indoor unit only,
1
0
0 – Unlock, 1 – lock
2
0
0 – Unlock, 1 – lock
3
0
0 – Unlock, 1 – lock
4
0
0 – Unlock, 1 – lock
1
0
0 – No use, 1 - Use
2
0
0 – No use, 1 - Use
3
0
0 – No use, 1 - Use
4
0
0 – No use, 1 - Use
1,2,3
0
-9 ~ 40 °C(15~104 °F)
4,5,6
0
-9.9 ~ 9.9 °C
1,2
-
0 ~ 16
3,4
-
0 ~ 16
1
0
0-1 °C, 1-0.5 °C, 2-0.1 °C
0-ON/OFF alternating operation,
1
0
1-Outdoor air cooling operation
for different temperature setting
3,4
15
5 ~ 15 °C (41~59 °F)
0 – Unchanged
1
0
1 – Factory setting
1~6
-
Software code
1~6
-
Software version
Unit
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
0.1 °C
0.1 °C
-
-
-
-
°C
-
-
-