13. Installation

Selecting installation location
f Choose a location with ventilation ducts or openings to remove the heat generated from the product and maintain the
surrounding temperature within: Hydro unit: 5 ~ 40 °C (41 ~ 104 °F), humidity 80 % Hydro unit HT: 5 ~ 35 °C (41 ~ 95 °F),
humidity 80 % .
f Choose a place where the structure can bear the weight and vibration of the DVM Hydro unit / Hydro unit HT .
f Choose a flat place that rainwater does not settle or leak .
f Choose a well ventilated place with sufficient space for repair and other services .
f Choose a place where you can easily connect the refrigerant pipes between the DVM Hydro unit / Hydro unit HT and outdoor
unit within allowable distance .
f Do not install this product in a place where it may corrode .
f Install the DVM Hydro unit / Hydro unit HT power and communication cables to the outdoor unit at least 1 m (3 .28 feet) away
from electric appliances such as TVs . I n some cases interference may occur even if there's more than 1 m (3 .28 feet) gap from
the electric appliances .
Space requirement
f When installing the product, make sure to secure minimum clearance with obstacles as shown below .
f When you install one product on top of the other one, secure at least 600 mm (23 .6 inch) of space on the water pipe side .
300 (11 .8)
518 (20 .4)
Product
Service space
(Side)
Service space (Front)
400 (15 .7)
Installation
space for pipe
Unit: mm (inch)