Power Requirements - Mitsubishi MELSEC-F FX1N-40MT-001 Hardware Manual

Table of Contents

Advertisement

FX1N Series Programmable Controllers
4.4

Power Requirements

AC Power Supply Units
Power supply
Max. allowable momentary power
failure period
Fuse (size) rating
In-rush current
Power consumption *1
*1 Includes the input current (7 or 5 mA per point).
DC Power Supply Units
Power supply
Max. allowable momentary power
failure period
Fuse (size) rating
In-rush current
Power consumption
FX
-14M
FX
-24M
1N
1N
100 - 240V AC +10%, -15%, 50-60Hz
10ms; If less than 10ms, the PLC will continue operation.
250V 1A
100V AC - Max. 15A for 5ms
200V AV - Max. 25A for 5ms
29W
30W
FX
-14M
FX
-24M
1N
1N
24V DC +20% ~ 12V DC -15% (28.8 ~ 10.2V DC)
5ms; If less than 5ms, the PLC will continue operation.
125 V 3.15A
24V DC - Max. 25A for 1ms
12V DV - Max. 22A for 0.3ms
13W
15W
Power Supply 4.
FX
-40M
FX
-60M
1N
1N
250V 3.15A (3A)
32W
35W
FX
-40M
FX
-60M
1N
1N
18W
20W
4-2