SECONDARY MENU ITEM DESCRIPTIONS
CONSTANT SETPOINT
FUNC
OSAT
Oat
LLT
Hlt
Pb1
Int
This indicates the mode of operation the
temperature controller is in. Common
modes are Oart, indoor\outdoor reset,
Cont, constant setpoint, and FDFO for a
water heater.
This menu item turns the outside air
enable\disable feature on or off. When
ON, an outside air temperature can be
chosen to enable or disable the unit.
This displays the outside air
temperature that the unit is enabled.
This parameter is displayed only when
OSAT is on.
This is Low Limit Temperature alarm.
This will put the temperature controller
into alarm if the outlet water temperature
goes below this setting.
This is High Limit Temperature alarm.
This will put the temperature controller
into alarm if the outlet water temperature
exceeds this setting.
This is the Proportional Band in
the feedback of the controller. This
feature is useful in correcting outlet
temperature errors when under steady
load conditions.
This is the integral rate, in minutes, for
the feedback of the controller. It is
adjusted with the
ENTER to accept changes.
ii
APPENDIX A
0
F for
and
. Press