Check codes Detected by Central Control Device
Check code
Main
Outdoor 7-segment display
remote
Check
Sub-code
controller
code
C05
C06
C12
Differs according to
nature of alarm-causing
trouble
P30
(L20 displayed.)
Location
Description
of
detection
Central
Central control
Continued
control
device
operation
device
transmission
trouble
Central
Central control
Continued
control
device reception
operation
device
trouble
General-
Batch alarm
Continued
purpose
for general-
operation
device
purpose
I/F
device
control interface
Central
Group control
Continued
control
follower unit
operation
device
trouble
Duplicated
Continued
central control
operation
address
– 116 –
Check code detection
System status
condition(s)
Central control device is
unable to transmit signal.
Central control device is
unable to receive signal.
Trouble signal is input to
control interface for general-
purpose devices.
Trouble occurs in follower
unit under group control.
([P30] is displayed on central
control remote controller.)
There is duplication in
central control addresses.
Check items (locations)
• Check for failure in central
control device.
• Check for failure in central
control communication line.
• Check termination
resistance setting.
• Check for failure in central
control device.
• Check for failure in central
control communication line.
• Check terminator resistor
setting.
• Check power supply for
devices at other end of
central control
communication line.
• Check failure in P.C.
boards of devices at other
end of central control
communication line.
• Check trouble input.
• Check check code of unit
that has generated alarm.
• Check address settings.