Toshiba MMU-UP0051MH-E(TR) Service Manual page 115

Table of Contents

Advertisement

Check code
Main
Outdoor 7-segment display
remote
Check
Sub-code
controller
code
1∗: Fan P.C.
board 1
P22
P22
2∗: Fan P.C.
board 2
1∗: Compressor
1 side
2∗: Compressor
2 side
P26
P26
1∗: Compressor
1 side
2∗: Compressor
P29
P29
2 side
P31
Location
Description
of
detection
Fan INV.
Outdoor fan
All stop
P.C. board
P.C. board
trouble
Compressor
IPM,
All stop
P.C. board
Compressor
shortcircuit
protection
trouble
Compressor
Compressor
All stop
P.C. board
position
detection circuit
trouble
Indoor unit
Other indoor
Stop of
trouble
corresponding
(group follower
unit
unit trouble)
– 115 –
Check code detection
System status
condition(s)
Protected operation of Fan
inverter P.C. board
Overcurrent is momentarily
detected during startup of
compressor.
Position detection is not
going on normally.
There is trouble in other
indoor unit in group,
resulting in detection of
E07/L07/L03/L08.
Check items (locations)
• Check fan motor.
• Check for failure in fan
P.C. board.
• Check connection of fan
motor connector.
• Check power voltage of
the main power supply.
• Check connector
connection and wiring on
compressor P.C. board.
• Check for failure in
compressor (layer
shortcircuit).
• Check for failure in outdoor
P.C. board ( Compressor).
• Check wiring and
connector connection.
• Check for compressor
layer short-circuit.
• Check for failure in
compressor P.C. board.
• Check indoor P.C. board.

Advertisement

Table of Contents
loading