Danfoss DSF090 Application Manual

Scroll compressors
Hide thumbs Also See for DSF090:
Table of Contents

Advertisement

Quick Links

Application Guide
Scroll compressors
DSF090 to DSF530
Single and manifold, 50-60 Hz - R32
www.danfoss.com

Advertisement

Table of Contents
loading

Summary of Contents for Danfoss DSF090

  • Page 1 Application Guide Scroll compressors DSF090 to DSF530 Single and manifold, 50-60 Hz - R32 www.danfoss.com...
  • Page 2: Table Of Contents

    Scroll compressors, DSF090 to DSF530 | Contents Contents Safety and warnings Introduction Product description Cut Away DSF090-200 Cut away DSF 270-530 How do IDVs work? Product identification Name Plate Nomenclature Compressors serial number Certificates, declarations, and approvals Low voltage directive 2014/35/EU...
  • Page 3 Scroll compressors, DSF090 to DSF530 | Contents Trio assemblies Mechanical connections Connection details Design compressor mounting Design piping Electrical connections Wiring connections Electrical specifications Application Manage oil in the circuit Manage sound and vibration Manage operating envelope Manage superheat Manage off cycle migration...
  • Page 4 Scroll compressors, DSF090 to DSF530 | Contents Terminal boxes, covers and T-block connectors Acoustic hoods Miscellaneous Tandem kits Trio kits Online support © Danfoss | Climate Solutions | 2023.06 AB309735209512en-000603 | 4...
  • Page 5: Safety And Warnings

    The purpose of this guideline is to help customers qualify compressors in the unit. You are strongly advise to follow these instructions. For any deviation from the guidelines, please contact Danfoss Technical Support. In any case, Danfoss accepts no liability as a result of the improper integration of the compressor into the unit by the system manufacturer.
  • Page 6: Introduction

    Scroll compressors, DSF090 to DSF530 | Introduction Introduction Product description DSF series scroll compressor benefit from an improved design to achieve the highest efficiency and increased life time. Cut Away DSF090-200 Figure 1: Cut Away DSF090-200 Intermediate discharge valves (IDVs) increase...
  • Page 7: Cut Away Dsf 270-530

    How do IDVs work? Figure 3: Intermediate Discharge Valve (IDV) Danfoss Intermediate Discharge Valves (IDVs) are located close to the discharge side of the compressor. They reduce excessive compression of refrigerant under part-load conditions while maintaining the same cooling capacity. The IDVs open when discharge pressure falls below the built-in optimization point.
  • Page 8: Product Identification

    PROTECTED BY DOMESTIC AND FOREIGN PATENTS Nomenclature Danfoss scroll compressor DSF for R32 is available as single compressor and can be assembled in tandem or trio combinations. The example below presents the compressor nomenclature which equals the technical reference as shown on the compressor nameplate.
  • Page 9: Compressors Serial Number

    Scroll compressors, DSF090 to DSF530 | Product identification Compressors serial number 12345678 Year code 8 Digit serial number Month code Plant assembly line code Table 1: Serial number code legend table Year code Month code Plant assembly line code Year...
  • Page 10: Certificates, Declarations, And Approvals

    Scroll compressors, DSF090 to DSF530 | Certificates, declarations, and approvals Certificates, declarations, and approvals DSF scroll compressors comply with the following approvals and certificates. Certificates are listed on: Documentation for Commercial Compressor | Danfoss Table 2: Approval and certificates Approval and certificates...
  • Page 11: Refrigerants

    Scroll compressors, DSF090 to DSF530 | Refrigerants Refrigerants General information When choosing a refrigerant, different aspects must be taken into consideration: • Legislation (now and in the future) • Safety • Application envelope in relation to expected running conditions • Compressor capacity and efficiency •...
  • Page 12: Technical Specification

    Scroll compressors, DSF090 to DSF530 | Technical specification Technical specification 50-60 Hz data, Single compressor Table 7: 50-60 Hz data, Single compressor Swept volume Displacement (50 Hz) Displacement (60 Hz) Oil charge Net weight Model /rev cu.in/rev cu.ft/h cu.ft/h DSF090 81.3...
  • Page 13: Performance Data

    Scroll compressors, DSF090 to DSF530 | Performance data Performance data R32 50-60 Hz, Single compressor Table 8: 50-60 Hz R32, Single compressor Nominal tons Nominal cooling capacity Power input E.E.R. 60Hz Model Btu/h Btu/h/W DSF090 19958 68096 6.69 2.99 10.19...
  • Page 14: Sound And Vibration Data

    Scroll compressors, DSF090 to DSF530 | Sound and vibration data Sound and vibration data Typical sounds and vibrations in systems can be broken down into the following three categories: • Sound radiation (through air) • Mechanical vibrations (through parts and structure) •...
  • Page 15: Mechanical Vibrations

    A compressor generates some vibrations that propagate into the surrounding parts and structure. The vibration level of a DSF compressor alone does not exceed 120 µm peak to peak for DSF090 to DSF200, and 154um peak to peak for DSF270 to DSF530.. However, when system structure natural frequencies are close to running frequency, vibrations are amplified due to resonance phenomenon.
  • Page 16: Operating Envelope Data

    Scroll compressors, DSF090 to DSF530 | Operating envelope data Operating envelope data Operating envelope data for DSF scroll compressors guarantees reliable operations of the compressor for steady-state operation. Steady-state operation envelope is valid for a suction superheat within 5K to 10K range at nominal Voltage.
  • Page 17 Scroll compressors, DSF090 to DSF530 | Operating envelope data Figure 7: Operating envelope R32 DSF270 to DSF530 Evaporating temperature (°F) S.H. = 10 K (18°F) S.H. = 5 K (9°F) Evaporating temperature (°C) CC-000543 Pressure settings Table 10: Pressure settings...
  • Page 18: Dimensions

    Scroll compressors, DSF090 to DSF530 | Dimensions Dimensions Single compressors Figure 8: Outline drawing number 1 Figure 9: Outline drawing number 2 Figure 10: Outline drawing number 3 Ø D Ø D Ø D 190.5mm Ø19.05mm (7.5 inch) (0.75 inch) 30°...
  • Page 19: Tandem Assemblies

    Scroll compressors, DSF090 to DSF530 | Dimensions Tandem assemblies Figure 11: Outline drawing number 1 Figure 12: Outline drawing number 2 Figure 13: Outline drawing number 3 Figure 14: Outline drawing number 4 Figure 15: Outline drawing number 5 Table 12: Tandem assemblies...
  • Page 20: Trio Assemblies

    Scroll compressors, DSF090 to DSF530 | Dimensions Motor voltage Outline drawing Tandem model Composition Cp1 + Cp2 code number inch inch inch inch inch DSF331U 3, 7, 9 DSF130+DSF200 33.46 16.85 22.83 9.45 9.53 8560167 DSF331U DSF130+DSF200 33.46 15.2 22.83 9.45...
  • Page 21 Scroll compressors, DSF090 to DSF530 | Dimensions Figure 18: Outline drawing number 8 Figure 19: Outline drawing number 9 Table 13: Trio assemblies Motor voltage Outline drawing Trio model Composition code number inch inch inch inch inch 1230 48.4 15.8 22.5...
  • Page 22: Mechanical Connections

    During operation, the maximum inclination from the vertical plane must not exceed 3 degrees. Single requirements DSF090-200 mounting Compressors DSF090-200 are delivered with rubber grommets and steel mounting sleeve used to isolated the compressor from the base frame. © Danfoss | Climate Solutions | 2023.06...
  • Page 23 Scroll compressors, DSF090 to DSF530 | Mechanical connections The grommets must be compressed until contact between the flat washer and the steel mounting sleeve is established. The required bolt size for the DSF090-200 compressors is HM8-40. This bolt must be tightened to a torque of 15Nm.
  • Page 24 Scroll compressors, DSF090 to DSF530 | Mechanical connections Figure 25: DSF 180E-400E and DSF285U-305U-330U mounting Tightening torque 15Nm Not supplied Φ8x75mm 0.31x2.95inch Tightening torque 15Nm 4mm (0.16 inch) thickness Supplied with the compressor Included in manifolding kit Not supplied Manifolding requirements DSF 215U-230U-255U-275U-300U-315U-331U-355U-375U mounting The compressors must be mounted with rigid mounting spacers on rails.
  • Page 25 Scroll compressors, DSF090 to DSF530 | Mechanical connections Table 15: Additionnal rigid spacer Additionnal rigid spacer Additional right spacer(to be added on the smallest compressor of the tan‐ dem) DSF215U-230U-255U-275U-315U-331U-355U-375U DSF300U 14mm Tandem requirements DSF465T-525T-600T mounting The compressors must be mounted with rigid mounting spacers on rails. Rubber grommets and spacers must be installed below the rails.
  • Page 26: Design Piping

    Scroll compressors, DSF090 to DSF530 | Mechanical connections Tightening torque 16Nm Tightening torque 15Nm Not supplied Φ10mm 4mm (0.16inch) thickness Tightening torque 50Nm Supplied with the compressor Tightening torque 55Nm Included in manifolding kit 5mm (0.2inch) thickness Not supplied Tandem requirements, DSF540E to DSF1590T mounting For parallel mounting, the compressors can be mounted directly on the rails.
  • Page 27 Scroll compressors, DSF090 to DSF530 | Mechanical connections Figure 31: Proper piping - Evaporator Evaporator CC-0043 0.5% slope 4m/s or more 8 to 12 m/s To condenser U-trap, as short as possible 4 m* Max. 4 m* Figure 32: Proper piping - Condenser...
  • Page 28 Scroll compressors, DSF090 to DSF530 | Mechanical connections Suction and oil equalization piping drawings must be respected (diameters, minimum straight lengths, …). Suction washer position Depending on manifold configuration, it is essential to equalize the pressure of compressor sumps. Hence, a suction washer must be added on certain compressors according to the table.
  • Page 29 Scroll compressors, DSF090 to DSF530 | Mechanical connections Outline Tandem Oil equali‐ Suction Washer in Tandem kit Composition Suction Discharge drawing Washer inner diameter model zation from suction of code no number Left DSF230E DSF115+DSF115 1"5/8 1"3/8 1"1/8 8560145 Not needed...
  • Page 30 Scroll compressors, DSF090 to DSF530 | Mechanical connections Trio models Table 17: Trio models Outline Oil equali‐ Suction Washer in Trio kit Trio model Composition Suction Discharge drawing Washer inner diameter zation from suction of code no number 26 mm (1.02 inch) Left 25 mm (0.98 inch)
  • Page 31 Scroll compressors, DSF090 to DSF530 | Mechanical connections Oil equalization design DSF 400X-470X-500X-525X The oil level is balanced by a pipe of 1"3/8 oil equalization line. In order to ensure best oil balance, the organ pipe need to be mounted inside the DSF130, DSF175, DSF200 oil equalization port as indicated on below picture.
  • Page 32 Scroll compressors, DSF090 to DSF530 | Mechanical connections Figure 38: DSF270, DSF530 Tightening torque 145 Nm Supplied with the compressor Included in tandem kit CC-000033 © Danfoss | Climate Solutions | 2023.06 AB309735209512en-000603 | 32...
  • Page 33: Electrical Connections

    DSF090-200(except DSF155/175 code3 DSF200 code3/7/9) The terminal box is provided with a Ø 25.5mm (φ1 inch) (ISO25) and a Ø 29mm (φ1.14) (PG21) knockouts. Figure 39: Wiring connections for DSF090-200(except DSF155/175 code3 DSF200 code3/7/9) Terminal box Ø 29mm (φ1.14inch) knockout Ø...
  • Page 34 Scroll compressors, DSF090 to DSF530 | Electrical connections DSF270-325-485-530 The terminal box is provided with 2 triple knockouts and 1 single knockout for power supply and 4 double knockouts for the safety control circuit. The 3 power supply knockouts accommodate the following diameters: •...
  • Page 35: Electrical Specifications

    N S1 S2 M1 M2 Safety circuit Thermistor connection Module power Electrical specifications Motor voltage Danfoss scroll compressors DSF are available in motor voltage listed below. Table 18: Motor voltage Frequency Motor voltage code Code 3 Code 4 Code 7...
  • Page 36 Any compressor damage related to this will not be covered by Danfoss warranty. In the same manner, cables must be selected in a way that ensures the terminal box temperature does not exceed 70 °C (158 °F).
  • Page 37 Scroll compressors, DSF090 to DSF530 | Electrical connections Max operating current Winding resistance Compressor model Ω DSF155 25.7 0.92 DSF175 26.4 0.83 DSF200 28.5 0.83 DSF270 0.62 DSF325 0.56 DSF485 0.28 DSF530 0.28 Table 21: Motor voltage code7 Max operating current...
  • Page 38 Motor protection DSF090 to DSF200 Compressor models DSF090 to 200 are provided with internal overload motor protection to prevent against excessive current and temperature caused by overloading, low refrigerant flow or phase loss. The protector is located in star point of motor and, should it be activated, will cut out all three phases. It will be reset automatically.
  • Page 39 DSF090 to DSF200 Compressor models DSF090 to 200 incorporates an internal reverse vent valve which will react when the compressor is run in reverse and will allow refrigerant to circulate through a by-pass from the suction to the discharge. Although reverse rotation is not destructive for these models, it should be corrected as soon as possible.
  • Page 40 Scroll compressors, DSF090 to DSF530 | Electrical connections Figure 47: In case of phase reverse error Figure 48: In case of phase loss error 120 ms 120 ms 120 ms 400 ms 500 ms 500 ms 1 s* 760 ms*...
  • Page 41: Application

    We can consider two means to reduce compressors sound radiations: Acoustic hoods are quick and easy to install and do not increase the overall size of the compressors. Acoustic hoods are available from Danfoss as accessories. Refer to the tables above for sound levels, attenuation and code numbers.
  • Page 42: Manage Operating Envelope

    If an unacceptable level is identified, a discharge muffler with the appropriate resonant volume and mass can be installed. Mitigation methods Mitigations methods: To ensure minimum vibrations transmission to the structure, strictly follow Danfoss mounting requirements (mounting feet, rails etc..). For further information on mounting requirements, please refer to section Design compressor mounting.
  • Page 43 No risk of operation beyond the application envelope. No DGT protection required. DSF090 to DSF200 have no integrated discharge temperature protection, an external protection is required. This external protection device can be a thermostat or a temperature sensor. The discharge gas temperature protection must trip the power supply when it reaches the setting point to protect the compressor from overheating.
  • Page 44: Manage Superheat

    Scroll compressors, DSF090 to DSF530 | Application System evaluation HP and LP must be monitored to respect operating envelope limitations. We consider two types of operating envelope management: Basic and Advanced. Table 25: System evaluation Basic Advanced • HP and LP switch •...
  • Page 45 Scroll compressors, DSF090 to DSF530 | Application Test, criteria and solutions Table 27: Test, criteria and solutions Test Purpose Test condition Pass criteria Solutions Liquid flood Steady-state Suction superheat >5 K (9 °F) Check expansion valve se- back test and the oil superheat shall not lection and setting.
  • Page 46: Manage Off Cycle Migration

    Scroll compressors, DSF090 to DSF530 | Application Dilution Chart - DSF090 to DSF200, R32 Figure 52: Dilution Chart (reference at 20 °C / 68 °F ambient temperature) Evaporating Temperature (°F) 22.5 40.5 17.5 31.5 Safe Area 12.5 22.5 13.5 Unsafe Area (60 sec max per hour) Evaporating Temperature (°C)
  • Page 47 The surface sump heater are designed to protect the compressor against off-cycle migration of refrigerant. For DSF090-200, the surface sump heater is located on the compressor shell. For better standby energy consumption, Danfoss provides 48W and 80W two optional surface sump heater. The selection of surface sump...
  • Page 48 Scroll compressors, DSF090 to DSF530 | Application Figure 55: DSF 270 to 530 The heater must be turned on whenever all the compressors are off. Crankcase heater accessories are available from Danfoss (see section Accessories and spare parts). Liquid line solenoid valve (LLSV) A LLSV is used to isolate the liquid charge on the condenser side, thereby preventing against charge transfer to the compressor during off -cycles.
  • Page 49: Power Supply And Electrical Protection

    Requirements • Protect the compressor from short circuit and overcurrent by a thermal magnetic motor circuit breaker set to Max. operating current or lower (see table in section Three phase electrical characteristics). For DSF090-200, phase sequence protection is strongly recommended.
  • Page 50 Scroll compressors, DSF090 to DSF530 | Application Figure 56: Compressor model DSF090 - 200 Figure 57: Compressor model DSF270 - 325 L1 L3 © Danfoss | Climate Solutions | 2023.06 AB309735209512en-000603 | 50...
  • Page 51 Scroll compressors, DSF090 to DSF530 | Application Figure 58: Compressor model DSF485 - 530 L1 L3 L2 Thermal magnetic motor circuit breaker Safety pressure switch Control circuit Compressor motor Crankcase heater Motor Protection Module Discharge gas thermistor (embedded in com-...
  • Page 52: Control Logic

    DGT) Cycle rate limit requirements Danfoss requires a minimum compressor running time of 2 minutes to ensure proper oil return and sufficient motor cooling. Additionally, compressor must not exceed 12 starts per hour. 12 starts per hour must not be considered as an average, this is the maximum number of starts acceptable to keep a good regulation accuracy during low load.
  • Page 53: Reduce Moisture In The System

    Scroll compressors, DSF090 to DSF530 | Application Cp 1 Compressor 1 Cp 2 Compressor 2 Heating Defrost start. Stop all compressors 4 Way Valve (4WV) stays in heating mode. EXV opened to transfer liquid from outdoor to indoor exchanger thanks to pressure difference.
  • Page 54: Assembly Line Procedure

    • driers water content capacity • system refrigeration capacity • system refrigerant charge For new installations with DSF compressors with polyolester oil, Danfoss recommends using the Danfoss DML (100% molecular sieve) solid core filter drier. Assembly line procedure Compressor storage Store the compressor not exposed to rain, corrosive or flammable atmosphere between -35 °C (-31 °F) and 70 °C...
  • Page 55 As per standards practice in the refrigeration industry, Danfoss Commercial Compressor recommend to use of silver cadmium free solder alloy and flux (added or flux coated rods). The significant silver content in these brazing alloy will help the brazing operation, providing an excellent fluidity and a limited heating temperature.
  • Page 56 Scroll compressors, DSF090 to DSF530 | Application The use of self-flux alloys (as phosphorous alloys) is not recommended by Danfoss. This type of brazing require a higher working temperature, that may overheat the connectors, damaging the thin layer of copper, resulting in phosphides creation and joint zone embrittlement.
  • Page 57: Commissioning

    Scroll compressors, DSF090 to DSF530 | Application • For the initial charge, the compressor must not run. • Charge refrigerant as close as possible to the nominal system charge. • This initial charging operation must be done in liquid phase between the condenser outlet and the filter drier.
  • Page 58: Dismantle And Disposal

    If Oil Top-up is needed, it must be done while the compressor is idle. Use the schrader connector or any other accessible connector on the compressor suction line. Always use original Danfoss POE oil 185SL from new cans. For more detailed information see “Lubricants filling in instructions for Danfoss Commercial Compressors”...
  • Page 59: Packaging

    Scroll compressors, DSF090 to DSF530 | Packaging Packaging Single pack Table 36: Single pack Length Width Height Gross weight Compressor model inch inch inch DSF090 22.2 18.5 28.3 DSF100 22.2 18.5 28.3 DSF115 22.2 18.5 28.3 DSF130 22.2 18.5 28.3 DSF155 22.2...
  • Page 60: Ordering

    Ordering Compressor code numbers Danfoss scroll compressors DSF can be ordered in either industrial packs or in single packs. Please use the code numbers from below tables for ordering. For compressors DSF270 to DSF530 use in single applications, flexible grommets are available as accessory kit 8156138.
  • Page 61 Scroll compressors, DSF090 to DSF530 | Ordering Table 39: Industrial pack Code no. Compressor model Connections Motor protection 380-415/3/50 208-230/3/60 575/3/60 380-400/3/60 460/3/60 DSF090 Brazed Internal 120H1907 120H1636 120H1905 120H1903 DSF100 Brazed Internal 120H1901 120H1638 120H1899 120H1897 DSF115 Brazed Internal...
  • Page 62: Accessories And Spare Parts

    Scroll compressors, DSF090 to DSF530 | Accessories and spare parts Accessories and spare parts Gaskets Table 40: Gaskets Code no. Description Application Packaging Pack size 8156132 Gasket, 1"3/4 Models with 1"3/4 rotolock connection Multipack 8156133 Gasket, 2"1/4 Models with 2"1/4 rotolock connection...
  • Page 63: Crankcase Heaters

    Scroll compressors, DSF090 to DSF530 | Accessories and spare parts Crankcase heaters Table 44: Crankcase heaters Code no. Description Application Packaging Pack size 120Z0388 80W 24V surface sump heater CE and UL DSF090 to 200 Multipack 120Z0389 80W 230V surface sump heater CE and UL...
  • Page 64: Terminal Boxes, Covers And T-Block Connectors

    Scroll compressors, DSF090 to DSF530 | Accessories and spare parts Terminal boxes, covers and T-block connectors Table 47: Terminal boxes, covers and T-block connectors Code no. Description Application Packaging Pack Size Service kit for terminal box 96 x 115 mm, includ-...
  • Page 65: Tandem Kits

    Scroll compressors, DSF090 to DSF530 | Accessories and spare parts Tandem kits Table 50: Tandem kits Code no. Description Application Packaging Pack Size 120Z0634 Suction washer, rigid spacer, organ pipe, gasket DSF260E-310E-DSF350E-DSF400E Single pack 120Z0692 Suction washer, rigid spacer, organ pipe, gasket...
  • Page 66: Online Support

    Online support Danfoss offers a wide range of support along with our products, including digital product information, software, mobile apps, and expert guidance. See the possibilities below. The Danfoss Product Store The Danfoss Product Store is your one-stop shop for everything product related—no matter where you are in the world or what area of the cooling industry you work in.