Content GENERAL INFORMATION ......4 Manage operating envelope ....31 Requirement ............31 Features.............5 High and low pressure protection ....32 Overview ..............5 Discharge temperature protection ....32 How do IDVs work? ..........5 System evaluation ..........33 Test, criteria and solutions ........33 Compressor model designation .....6 Nomenclature ............
Danfoss Technical safety and reliability. Related instructions are highlighted with the following icons: Support. In any case, Danfoss accepts no liability as a result of the improper integration This icon indicates instructions to avoid of the compressor into the unit by the system safety risk.
Organ pipe master oil circulation in manifold configuration. DSF090-200 How do IDVs work? Danfoss Intermediate Discharge Valves (IDVs) are located close to the discharge side of the compressor. They reduce excessive compression of refrigerant under part-load conditions while maintaining the same cooling capacity. The IDVs open when discharge pressure falls below the built-in optimization point.
Compressor model designation Danfoss scroll compressor DSF for R32 is available which equals the technical reference as shown as single compressor and can be assembled on the compressor nameplate. Code numbers in tandem or trio combinations. The example for ordering are listed in section “Ordering below presents the compressor nomenclature information”.
190.5mm (7.5 inch) 30° Compressor model Outline drawing number inch mm inch mm inch inch mm inch inch inch DSF090-100 9.57 485 19.09 235 9.25 451 17.76 180 7.09 9.06 9.06 8560176 DSF115-175 9.57 542 21.34 278 10.94 509 20.04 180 7.09...
Dimensions Tandem assemblies Tandem model Composition Outline drawing number inch inch inch inch inch DSF180E DSF090+DSF090 33.46 15.12 19.96 8560144 DSF200E DSF100+DSF100 33.46 15.12 19.96 8560144 DSF230E DSF115+DSF115 33.46 15.12 22.24 8560145 DSF260E DSF130+DSF130 33.46...
Dimensions Trio assemblies Outline drawing Trio model Composition number inch inch mm inch inch mm inch 1230 48.4 15.8 571 22.5 8560172 DSF465T 3 x DSF155 1326 52.2 15.8 571 22.5 24.5 8560172 1230 48.4 15.8 571 22.5 8560172...
Electrical data, connections and wiring Motor voltage Danfoss scroll compressors DSF are available in only one motor voltage as listed below. Motor voltage code Code 4 Nominal voltage 400V-3ph 50Hz Voltage range* 360-440V Nominal voltage 460V-3ph 60Hz Voltage range* 414-506V * The voltage range indicates where the compressor can run in the majority of the application envelope.
The temperature inside the terminal box necessary. Any compressor damage related to must not exceed 70°C (158°F). Consequently, this will not be covered by Danfoss warranty. In if the compressor is installed in an enclosure, the same manner, cables must be selected in a...
Coefficient a = 234.5 resistance must be corrected using the following Motor protection DSF090 to 200 Compressor models DSF090 to 200 are provided Then it must be set below MCC value (at max with internal overload motor protection operating current):...
CE 0062 or CE 0038 or CE0871 All DSF models (European Directive) All DSF models (Underwriters Laboratories) Other approvals / certificates Contact Danfoss Low voltage directive Products DSF models 2014/35/EU Declaration of conformity Contact Danfoss Machines directive Products...
SYSTEM DESIGN Design piping General requirements Proper piping practices should be employed to: 2. Avoid condensed liquid refrigerant from draining back to the compressor when stopped 1. Ensure adequate oil return, even under (discharge piping upper loop). For validation minimum load conditions (refrigerant speed, tests see section “Manage off...
(diameters, indicated in the following table. minimum straight lengths, …) Outline drawing Tandem model Composition Suction Discharge Oil equalization Kit tandem code no number DSF180E DSF090+DSF090 1"5/8 1"3/8 1"1/8 120Z0634 8560144 DSF200E DSF100+DSF100 1"5/8 1"3/8 1"1/8 120Z0634...
Compressor1 (Cp1) (Cp1) Kit code no to Washer inner Washer in suction Tandem model Suction from Washer reference order diameter Left DSF090 + DSF090 DSF180E 120z0634 Right Left DSF100 + DSF100 DSF200E 120z0634 Right Not needed Left DSF115 + DSF115...
Page 19
Design piping Kit code no to Washer inner Washer in suction Tandem model Suction from Washer reference order diameter Left 5312497P01 25mm (0.98inch) DSF130 + DSF175 DSF305U 120Z0692 Right 5312497P01 25mm (0.98inch) Left DSF155 + DSF155 DSF310E 120Z0634 Not needed Right Left 5312497P03...
Page 20
Design piping On trio models Right suction Left suction Compressor 1 Compressor 3 (Cp1) (Cp3) Compressor 2 Compressor 2 (Cp2) (Cp2) Compressor 3 Compressor 1 (Cp3) (Cp1) Kit code no Washer Washer inner Washer in Trio model Suction from to order reference diameter suction of...
Design piping Oil equalization design Even/Uneven/Trio The oil level is balanced by a pipe of 1"1/8 oil port as indicated on below picture. To connect equalization line. the equalization line on rotolock connections, the organ pipe adaptor and teflon gasket are In order ensure best oil balance, the organ pipe included in the tandem kit must be used.
Page 22
Design piping DSF400X-470X-500X- The oil level is balanced by a pipe of 1"3/8 oil To connect the equalization line on rotolock 525X equalization line. connections, the organ pipe, adaptor sleeves, Teflon gaskets included in the tandem accessory In order to ensure best oil balance, the organ kit must be used.
Steel mounting between the flat washer and the steel mounting sleeve 15mm sleeve is established. The required bolt size for Rubber grommet (0.59 inch) the DSF090-200 compressors is HM8-40. This bolt must be tightened to a torque of 15Nm. AB367332784529en-000101...
Design compressor mounting Manifolding requirements DSF 180E-400E The compressors must be mounted with rigid The rigid mounting spacers are included in mounting mounting spacers on rails. Rubber grommets and tandem accessory kits. The rubber grommets are spacers must be installed below the rails. supplied with compressor.
Design compressor mounting DSF 315U-331U-355U-375U The compressors must be mounted with rigid Because for oil balance port height, DSF115/130/ mounting mounting spacers on rails. Rubber grommets and 155/175 is 7mm lower than DSF200, in order spacers must be installed below the rails. to ensure that the oil equalization connection is at the same level for both compressors, an The rigid mounting spacers are included in...
Design compressor mounting DSF465T-525T-600T The compressors must be mounted with rigid The rigid mounting spacers and rubber mounting spacers on rails. Rubber grommets and grommets are included in tandem accessory kits. spacers must be installed below the rails. Tightening torque 15Nm Not supplied HM8mm 0.31 inch...
Design compressor mounting DSF400X-470X-500X- The large compressor, DSF270,325, is mounted spacer, and the beams are mounted with rigid 525X mounting with rigid spacers on the rails. The DSF130, spacers on the rails. Rubber grommets and 175,200 compressor is fixed on beams by rigid spacers must be installed below the rails.
2. Check that manifold piping is Check oil condensation and nominal capacity compressors are running and when conform to Danfoss requirements. balancing condition all compressors of the circuit are 3. Integrate a function in control...
60 H Compressor model Sound power Sound power dB(A) dB(A) DSF090 DSF100 DSF115-175 DSF200 Sound power and attenuation are given at ARI conditions, measured in free space • For compressors running simultaneously, - the global sound level of “n” identical compressors is:...
Solutions to change natural frequencies are to 1. To ensure minimum vibrations transmission to work on structure stiffness and mass (brackets, the structure, strictly follow Danfoss mounting metal sheet thickness or shape…) Gas pulsation DSF has been designed and tested to ensure...
S.H. = 5 K (9°F) Evaporating temperature (°C) Operating envelope Evaporating temperature (°F) DSF090- 130 S.H. = 5 K (9°F) Evaporating temperature (°C) Note: The application envelope of a even/uneven/cross-platform manifold results in the conjunction of map limitations of compressors composing the tandem.
Discharge temperature protection DSF090 to DSF200 For DSF090 - 200 compressors, the external The DGT protection must be attached to the discharge gas (DGT) protection is required, since discharge line within 150mm (5.91inch) fromthe the high and low pressure protection settings do...
Manage operating envelope System evaluation HP and LP must be monitored to respect operating envelope limitations. We consider two types of operating envelope management: Basic: Advanced: • HP and LP switch • HP and LP sensor • MOP (Max Operating Pressure) ensured by expansion •...
Manage superheat During normal operation, refrigerant enters Liquid flood back can cause oil dilution and, in the compressor as a superheated vapor. Liquid extreme situations lead to liquid slugging that flood back occurs when a part of the refrigerant can damage the compressor. entering the compressor is still in liquid state.
Page 35
The sensor must also be correctly thermally insulated from the ambiance. The Oil superheat is defined as: (Oil temperature - Evaporating temperature) DSF090-200 Dilution Chart (reference at 20°C / 68°F ambient temperature) Evaporating Temperature °F 22.5 40.5 17.5...
The surface sump heater are designed to protect the compressor against off-cycle migration of refrigerant. For DSF090-200, the surface sump heater is located on the compressor shell. For better standby energy consumption, Danfoss provides 48W and 80W two optional surface sump heater.
Page 37
Pump-down must be set higher than 1.7bar(g) (25 psig). Charge limits are defined in the table below : Refrigerant charge limit Models Composition DSF090 DSF100 DSF115 Single DSF130 DSF155 DSF175 DSF200 DSF180E...
(e.g. (see table in section “Three phase electrical characteristics”). For DSF090-200, phase seasonal shutdown). sequence protection is strongly recommended. • HP safety switch, DGT protection must be wired...
12 hours, then manual reset. Cycle rate limit Danfoss requires a minimum compressor running Additionally, compressor must not exceed 12 requirements time of 2 minutes to ensure proper oil return and starts per hour. 12 starts per hour must not be sufficient motor cooling.
Control logic Pump-down logic Pump down is initiated prior to shutting • One shot pump down (preferred): when recommendations down the last compressor on the circuit by last compressor of the circuit stops, suction de-energizing a liquid line solenoid valve presssure is decreased 1.5bar (22psi) below or closing electronic expansion valve.
For new installations with DSF compressors with and type of drier is required. Important selection polyolester oil, Danfoss recommends using the criteria’s include: Danfoss DML (100% molecular sieve) solid core • driers water content capacity, filter drier. • system refrigeration capacity, •...
Handling Each Danfoss DSF scroll compressor is • For tandem and trio assemblies, use a spreader equipped with two lift rings on the top shell. bar and all compressor rings as shown in picture •...
The use of self-flux alloys (as phosphorous alloys) • Clean up connections with degreasing agent is not recommended by Danfoss. This type of brazing require a higher working temperature, • Flow nitrogen through the compressor. • It is recommended to use double-tipped torch...
• Do not exceed the following pressures indicated • Always use an inert gas such as Nitrogen or in table below Helium. Maximum compressor test pressures DSF090-200 53,6bar (g) (778psig) Maximum compressor test pressure high side (HP) HP-LP<37bar (537psi) 36.7bar (g) (533psig) Maximum compressor test pressure low side (LP) LP-HP<5bar (73psi)
• Correct superheat and subcooling. • Current draw of individual compressors within Always use original Danfoss POE oil 185SL from acceptable values (max operating current). new cans. • No abnormal vibrations and noise.
Dismantal and disposal Danfoss recommends that compressors and compressor oil should be recycled by a suitable company at its site. AB367332784529en-000101...
Ordering codes Compressor code numbers Danfoss scroll compressors DSF can be ordered Compressors DSF090 to DSF200 are delivered in either industrial packs or in single packs. Please with flexible grommets. use the code numbers from below tables for ordering. Single pack Code no.
Page 49
- Tubings, according to specific outline drawings. built. To complete an assembly in the field, you - Manifolding accessory kit indicated below will need: - Compressors. Tandem Model Suction From Tandem Kit Code No. Left DSF180E DSF090 DSF090 120z0634 Right Left DSF200E DSF100 DSF100 120z0634 Right...
Page 50
Ordering codes Trio kits By default, DSF are not factory-built. - Manifolding accessory kit indicated below To complete an assembly in the field, you will - Compressors. need: - Tubings, according to specific outline drawings. Trio model Suction from Trio Kit code No Left DSF465T DSF155...
48W 460V surface sump heater CE and UL Single pack 120Z0671 48W 575V surface sump heater CE and UL Single pack DSF090 to 200 120Z0388 80W 24V surface sump heater CE and UL Multipack 120Z0389 80W 230V surface sump heater CE and UL...
Page 52
Multipack 8156129 Gasket for oil sight glass, 1"1/8 (white teflon) Multipack 7956005 Gasket for oil sight glass, 1"1/8 (white teflon) Multipack 8154001 Danfoss Commercial Compressors blue spray paint Single pack Tandem kits Code no. Description Application Packaging Pack Size 120Z0634...
Page 53
Updates Release date(Year/month) Guideline codification number List of changes Reason for change 2021.01 First release...