EGN100
• Device to be installed only by a qualified
electrician according to the installation
standards applicable in the country.
• Not suitable for controlling SELV loads.
Product Presentation
The EGN100 time switch is a clock with weekly and
annual electronic programming that automatically
controls different loads.
Examples of applications: street lighting, neon signs,
shop windows, monuments, facades etc.
The integrated astronomical clock can be set to
switch loads according to sunset and sunrise times.
The EGN100 switch is also compatible with the Hager
Quicklink radio product line.
The connection of an EEN002 / EEN003 twilight
sensor (optional) makes it possible to switch the loads
according to brightness.
Programming is performed with a mobile terminal
via Bluetooth
technology using the configuration
®
application (iOS and Android) available as a free
download.
The keys
C1/FCT (key and LED) used for:
• output control;
• programming the RF
module operating mode,
• Bluetooth
reset.
®
EGN100
BLE/CFG (key and LED) used for:
• Bluetooth
®
activation and
deactivation (BLE),
• RF module configuration;
• Resetting parameters and RF
modules.
Image 1: Presentation of keys
Main features
• Product delivered with updated time and day (Paris).
• Programming by application via Bluetooth
technology:
- automatic daylight savings time change;
- astronomical mode;
- programming by day or group of days;
- 100 program steps On, Off, pulses
• Permanent overrides On or Off.
• Temporary overrides On or Off.
• Exceptions (temporary, permanent or delayed) can
be activated remotely using a push button.
• Twilight switch function via an EEN002 or EEN003
wired brightness sensor.
1
z Multi-function Time Switch
1 Channel Bluetooth
Additional information is available by
scanning the displayed QR code with
your mobile terminal.
Hager Mood
Before connecting the cell, or before
carrying out any operations on it, cut the
230 V power supply to the clock.
Connection diagram
L
N
1
Override input
or exception
2
Brightness sensor
Figure 2: EGN100 connection diagram (1 output)
Technical specifications
Electrical specifications
• Supply voltage: 230 V~ +10/-15%
and 240 V~ ± 6%
• Network frequency: 50/60 Hz
• Consumption: < 170 mW
• Output: 1 non-insulated changeover contact with
a voltage measurement of < 1 V for zero-crossing
switching.
• Max. breaking capacity: AC1 μ 10A 230 V~
• Incandescent light bulbs:
- Power relay with normally open contact/2300 W
- Power relay with normally closed contact/1500 W
• Halogen lamps: 230 V~ 2300 W
• Fluorescent tubes, compensated // (max. 45 μF):
- Power relay with normally open contact/400 W
- Power relay with normally closed contact/300 W
• Fluorescent tubes, uncompensated, series
compensated: 1000 W
• Compact fluorescent lamps and LED lamps:
- Power relay with normally open contact/400 W
- Power relay with normally closed contact/300 W
• Min. breaking capacity: AC1 100 mA 230 V~
• Rated shock voltage: 4 kV
• Maximum switching speed at full load: 6 switching
cycles/minute
Functional features
• Programming capacity: 100 steps
• Min. time between 2 steps: 1 minute
• Precision of operation: ± 0.25 s / day
radio frequency: 2.4 - 2.483 GHz
• Bluetooth
®
- Max. transmitting power: 10 mW
®
- Range: 10 m in free field
- Version: 4.2
• Mobile/PC terminal configuration
- iOS version equal to or greater than 8
.
- Android version equal to or greater than 5.1
- Windows version equal to or greater than 10
- Bluetooth
®
: version equal to or greater than 4.2
• Quicklink radio frequency: 868 - 870 MHz
- Max. transmitting power: 25 mW
- Receiver category 2
- Range: 100 m in free field
• Insulation class: 2
• Action type: 2B
• Software class: Class A
• Ball test T°: 75 °C
• Upstream protection: 10 A circuit breaker
• Stated voltage and current for EMC emissions
®
testing: 230 V~ / - 0.5 A
• Protection class: IP20 (case), IP30 (case under
faceplate)
• Impact resistance: IK04
Battery
• Power reserve: 10 years
• Non-replaceable and non-rechargeable
Case
• Dimensions: 18 mm / 1 module
• DIN rail mounted independent product according to
EN 60715
Environment
• Operating T° -5 °C to +45 °C
• Storage T° -25 °C to +70 °C
• Relative humidity: 95 % to 20 °C
• Pollution category 2
Connection with screw terminals
• Rigid 0.2 to 4 mm
• Flexible 0.2 to 2.5 mm
• Screw recess: PH1
Initial set-up
BLUETOOTH
To program and set the clock with a mobile terminal,
the Bluetooth
Each time the BLE key is pressed (> 2 s) the function
is enabled or disabled.
1
5
3
7
BLE
2
6
Blue
4
8
Blue
Figure 3: LED operation and status
CONFIGURATION APPLICATION
To set the clock, use the application and perform the
installation as described below.
1. Directly access the application's download link by
scanning the QR code printed on the instructions
with a mobile terminal.
2. Download and install the configuration application.
3. Check that Bluetooth
/ BLUETOOTH).
4. Pair your mobile terminal and your clock via the
Bluetooth
5. Program your product via the application. To do this,
follow the application instructions to configure the
clock.
Settings via the configuration application:
Settings for the use of your clock are available via the
application as settings of:
• date and time;
• astronomical clock;
• wired input;
• daylight savings time change;
• twilight sensor.
2
2
The product must not be in "Quicklink"
configuration mode.
function must be activated.
®
LED status / Operation
off
Bluetooth
disabled
®
Bluetooth
enabled
®
Bluetooth
assembled and
®
connected
is enabled (see Initial set-up
®
application.
®
6LE005554C

Advertisement

loading

Summary of Contents for hager EGK101

  • Page 1 The integrated astronomical clock can be set to is enabled or disabled. switch loads according to sunset and sunrise times. The EGN100 switch is also compatible with the Hager LED status / Operation Quicklink radio product line. The connection of an EEN002 / EEN003 twilight...
  • Page 2 DELETING A FUNCTION Resume the principle described in the previous chapter Function configuration, in step 3, select the “delete” function and then confirm it. Hager Controls S.A.S., 33 rue Saint-Nicolas, B.P. 10140, 67703 SAVERNE CEDEX, France - www.hager.com Hager 11.2020 - 6LE005554C...

This manual is also suitable for:

Egn100Egk100