1 channel time switch - weekly cycle

Advertisement

Available languages

Available languages

Quick Links

Æ
§
1 channel time switch -
weekly cycle
pr og
ON
au to
nu
ma
OFF
7
6
t
5
re se
4
3
r
2
en te
1
on
of f
EG170
Working principle :
Time and day setting :
The EG170 is a time switch for the automatic
control of electrical loads.
It is fully programmable with a maximum of 20
program steps. Each program step can be
applied to one or several days, maximising the
use of each memory location.
The front cover is sealable preventing
unauthorised access after completion of
programming.
Warning : at the beginning of use, please
reset the device in order to clear the memory
on
before programming.
This is achieved by using a pen to push the
reset button.
Presentation :
1. Move mode selector to
2. Select with key "1" to "7" , the actual day
(1=Monday, 2 = Tuesday .)
3. Input time with buttons "+" and "-".
2
Important :
1
The clock starts when exiting the time setting mode.
4
prog
auto
OFF
manu
3
Programming :
5
1
2
3
4
5
6
7
on
reset
enter
off
6
7
8
9
Display :
Œ
time

on
circuit status (ON or OFF)
Ž
day of the week
(1 = Monday, 2 = Tuesday ....)
Buttons :

Mode selector : to select one of the
1. Move mode selector to "prog".
following modes :
2. Select with keys "1" to "7" the day(s) assigned
time setting
to this program step. An arrow appears
prog programming
above each day concerned.
auto running mode
3. Input switching time with buttons "+" and "-".
manu manual override
4. Input the type of switching with button "on/off"

"1" to "7" : selection of the days
(for the first action ON is automatically proposed).
"on/off" : chooses whether the circuit
5. Enter this program step with button "enter".
is on or off
Program additional time settings by repeating
"+" and "-" : changes settings
steps 2 to 5.
"enter" : to confirm
Important :
"reset"
To activate the program, move mode selector to
"auto".
Running Auto mode
This mode is the current displaying mode.
It does not allow any modification.
Move mode selector to "auto".
Display of the time, the day and the state of
the channel.
1
User instruction
To check your program :
1. Move mode selector to "prog".
2. Press the "enter" key repeatedly to display
the different program steps (switching time,
days of the week and state of the channel
ON or OFF).
prog
auto
manu
To modify or delete a program step :
1
2
3
4
5
6
7
reset
enter
off
1
2
3
4
on
off
1. Move mode selector to "prog".
2. Press "enter" repeatedly and select the
program step to modify or to delete.
3. Modify :
- switching time with keys "+" or "-"
- days assigned with keys "1" to "7".
ON
prog
(an arrow flashes above all days assigned,
auto
press once to add a day, press twice to
manu
cancel).
- state of the channel with key "on/off".
To delete a program step, press keys "1" to "7"
1
2
3
4
5
6
7
in order to cancel all days assigned.
reset
enter
4. Confirm with the "enter" key.
off
To override the output :
Permanent override :
1
2
3
4
on
off
1. Move mode selector to "manu".
2. Select the state of the output with key
"on/off".
To switch back to automatic mode, move
mode selector to "auto".
Timed override :
ON
1
3
4
5
6
2
on
off
ON
prog
auto
manu
1. Move mode selector to "manu".
2. Select the state of the output with key
"on/off".
5
6
7
3. Input with key "+" and "-" the override duration :
reset
from 1 to 23 hours by steps of 1 hour.
enter
Then from 1 to 27 days by steps of 1 day.
4. Move mode selector to "auto".
The state indication is flashing. This means a
timed override. Return to the initial program
after the duration.
To cancel the timed override :
ON
1
2
3
4
5
6
on
ON
off
prog
auto
manu
1. Move mode selector to "manu".
2. Press key "-" or "+" until display -h.
5
6
7
3. Move mode selector to "auto" to switch
reset
back to automatic mode.
enter
To reset the time switch :
Press "reset" to clear the program.
Technical specifications :
Electrical characteristics :
- supply voltage : 230V AC +10/-15% 50/60Hz
- output : 1 changeover contact
μ 16A - 250V AC1.
μ 3A - 250V cos ϕ = 0,6
1000 W incandescent lighting
prog
auto
- power consumption : 1 VA
manu
- protection degree : IP20
- insulation class : II
Functional characteristics :
7
- accuracy : ± 1sec. / day at 20 °C
reset
- operating reserve : lithium battery, total of
enter
three years.
Environment :
Operating temperature : -10 to +50 °C
Storage temperature :
-10 to +50 °C
Connection tunnel terminals :
2
flexible : 0,5 to 2.5 mm
2
rigid : 0,5 to 4 mm
Dimensions : 3 modules (3x17,5mm)
Electrical connections :
L
N
EG170
1
2
3 4 5 6
prog
auto
manu
7
reset
enter
Warranty
GB
A warranty period of 24 months is offered on hager products,
from date of manufacture, relating to any material of manufac-
turing defect. If any product is found to be defective it must be
returned via the installer and supplier (wholesaler). The warranty
is withdrawn if :
- after inspection by hager quality control dept the device is
found to have been installed in a manner which is contrary to
IEE wiring regulations and accepted practice within the industry at
the time of installation.
- the procedure for the return of goods has not been followed.
Explanation of defect must be included when returning goods.
6E 6127.c

Advertisement

loading

Summary of Contents for hager EG170

  • Page 1 To reset the time switch : This mode is the current displaying mode. A warranty period of 24 months is offered on hager products, It does not allow any modification. from date of manufacture, relating to any material of manufac- 1.
  • Page 2 W celu anulowania sterowania specjalnego, rującego. ustawić suwak w pozycji “auto”. Hager SAS - 132 bld d’Europe - BP 78 - 67 212 Obernai cedex (FRANCE) - Tél. +333 88 49 50 50 - www.hagergroup.net 6E 6127.c...