Safety Characteristic Data - Pilz PNOZ e1vp Operating Manual

Safety relays
Table of Contents

Advertisement

PNOZ e1vp

Safety characteristic data

Operating
EN ISO
Mode
13849-1:
2015
PL
SC output
via logic in-
put
PL e
SC output
via 2-ch. in-
put circuit
PL e
All the units used within a safety function must be considered when calculating the safety
characteristic data.
Remove plug-in terminals
Procedure: Insert the screwdriver into the housing recess behind the terminal and lever the
terminal out.
Do not remove the terminals by pulling the cables!
Operating Manual PNOZ e1vp
21236-EN-06
NOTICE
You must comply with the safety-related characteristic data in order to
achieve the required safety level for your plant/machine.
EN ISO
EN 62061
13849-1:
SIL CL
2015
Category
Cat. 4
SIL CL 3
Cat. 4
SIL CL 3
INFORMATION
A safety function's SIL/PL values are not identical to the SIL/PL values of
the units that are used and may be different. We recommend that you use
the PAScal software tool to calculate the safety function's SIL/PL values.
EN 62061
IEC 61511
PFH
[1/h]
SIL
D
3,61E-09
SIL 3
3,44E-09
SIL 3
IEC 61511
EN ISO
13849-1:
PFD
2015
T
[year]
M
5,82E-05
20
4,53E-05
20
35