PZE X4V8
Environmental data
Protection type
Mounting area (e.g. control cabinet)
Housing
Terminals
Mechanical data
Mounting position
Mechanical life
Material
Bottom
Front
Top
Connection type
Mounting type
Conductor cross section with screw terminals
1 core flexible
2 core with the same cross section, flexible with
crimp connectors, no plastic sleeve
2 core with the same cross section, flexible without
crimp connectors or with TWIN crimp connectors
Torque setting with screw terminals
Dimensions
Height
Width
Depth
Weight
Where standards are undated, the 2014-07 latest editions shall apply.

Safety characteristic data

Operating
EN ISO
mode
13849-1:
2008
PL
Safety con-
tacts,
delayed <30
s
PL d
Operating Manual PZE X4V8
1003204-EN-07
NOTICE
You must comply with the safety-related characteristic data in order to
achieve the required safety level for your plant/machine.
EN ISO
EN 62061
13849-1:
SIL CL
2008
Category
Cat. 3
SIL CL 2
IP54
IP40
IP20
Any
10,000,000 cycles
PPO UL 94 V0
ABS UL 94 V0
PPO UL 94 V0
Screw terminal
Fixed
0,2 - 4 mm², 24 - 10 AWG
0,2 - 2,5 mm², 24 - 14 AWG
0,2 - 2,5 mm², 24 - 14 AWG
0,6 Nm
87 mm
45 mm
121 mm
345 g
EN 62061
IEC 61511
PFH
[1/h]
SIL
D
2,48E-09
SIL 2
IEC 61511
EN ISO
13849-1:
PFD
2008
T
[year]
M
1,47E-05
20
14