SIMATIC RF185C, RF186C, RF188C, RF186CI, RF188CI
Operating Instructions, 06/2019, C79000-G8976-C512-02
Error description
Communication error between Ident profile and communications module. Handshake error.
Possible causes / action to be taken:
UDT of this communications module is overwritten by other program sections.
Check the parameter settings of the communications module in the UDT.
Check the Ident profile command that causes this error.
After eliminating the error, execute the "INIT" command.
Backplane bus / PROFIBUS DP / PROFINET error occurred
This error is only indicated when access monitoring has been enabled in the PROFIBUS con-
figuration.
Possible causes / action to be taken:
Backplane bus / PROFIBUS DP / PROFINET bus connection was interrupted (wire break
on the bus; bus connector on the communications module was briefly unplugged)
Backplane bus / PROFIBUS DP / PROFINET master no longer addressing communica-
tions module
Execute the "INIT" command.
The communications module has detected a frame interruption on the bus. The backplane
bus, PROFIBUS or PROFINET may have been reconfigured (e.g. with HW Config or TIA
Portal).
Firmware error
Possible causes:
The firmware update was not run completely.
Internal communications error of the communications module/reader
Possible causes / action to be taken:
Connector contact problem on the communications module / reader
Hardware of the communications module/reader has a defect; → Send in communications
module/reader for repair.
After eliminating the error, execute the "INIT" command.
Internal monitoring error of the communications module/reader
Possible causes / action to be taken:
Program execution error on the communications module / reader
Switch supply voltage to communications module/reader off and on again.
After eliminating the error, execute the "INIT" command.
The current command was aborted by the "WRITE-CONFIG" ("INIT" or "SRESET") command for
the bus connector was pulled.
Possible causes:
Communication with the transponder was aborted by "INIT".
This error can only be reported if there is an "INIT" or "SRESET".
Incorrect sequence number order (SN) on the reader/communications module
Incorrect sequence number order (SN) in the Ident profile
Invalid data block number (DBN) on the reader/communications module
Invalid data block number (DBN) in the Ident profile
Service and maintenance
10.2 Error messages
139