NOTE:
If an error occurs during the backup process, the display
screen shows a negative value.
Refer to diagnostic code 137 to determine the cause of the
error (see section "List of error codes" on page 56).
It is advisable to perform a backup every time
that a parameter is changed, after checking
that the modification carried out is correct.
WARNING

6.10.2 Restore

Use this procedure when replacing equipment
with a parts code. In this way it is possible to have
the default parameters already memorised or
those memorised during the start-up.
WARNING
This procedure cannot be carried out on
equipment coming from other burners.
To perform the restore procedure, proceed as follows:
 access the Parameters Level referring to "Access procedure
with password" on page 37 .
The display screen displays the parameters group 400.
P
With the key "-":
Select the parameters group 000:
P
The 000 parameter blinks, confirm using the "i/reset" key:
The display screen shows parameter 050 blinking:
P
Confirm with the key "i/reset":
20081760
Start-up, calibration and operation of the burner
V
h
min
s
%
h min s
%
/reset
h min s
%
/reset
The parameter bAC_UP appears on the display screen:
P
With the key "+"
select the rEStorE parameter
P
Confirm with the key "i/reset":
The display shows the following value.
P
Use the button "+":
The value will be set to 1. Value 1 is flashing:
P
confirm with the button "i/reset" to activate the restore process.