5.9

Gas butterfly valve

If necessary, replace the gas butterfly valve. The correct position
is shown in Fig. 18.
5.10

Combustion head adjustment

Rotate the screw 1) until the notch you have found corresponds
with the front surface of the screw itself.
The combustion head is opened by turning the screw 1) anti-
clockwise.
The combustion head is closed by turning the screw 1) clockwise
(Fig. 19)
Central air adjustment:
The factory setting is shown in Tab. L
Burner
RS 310
Set-point
7
Normally the calibrations indicated in Tab. L
should not be changed.
WARNING
In the event that the specific application requires a particular ad-
justment, it is possible to change the central air flow rate using the
ring nut 4)(Fig. 20). To carry out this operation loosen the screws
5)(Fig. 20) and move the ring nut 4)(Fig. 20). When finished, lock
the screws 5) again (Fig. 20).