Minimum Framing Dimensions - Rear Vent Configuration - FireplaceXtrordinair 864 TRV 31K Installation Manual

With ember-glo lights
Hide thumbs Also See for 864 TRV 31K:
Table of Contents

Advertisement

12

Minimum Framing Dimensions - Rear Vent Configuration

HINT: place the fireplace so the center
line is at least 5" (127mm) from both
vertical framing members at the rear (this
allows the vent to pass through the
framing without modfications)
Route the
electrical line to
a position to the
left rear of the
fireplace.
Minimum enclosure height = 38-1/2" (978mm)
© Travis Industries
Installation
38-1/2"
978mm
41-1/4"
1048mm
8/17/2018 - 1482
(for qualified installers only)
Included Firestop (required)
Part # 93006094
38"
965mm
25-3/4"
654mm
20-3/4"
528mm
Vent Clearances 8" (203mm) dia. Vent:
1" (25mm) to the sides, 1" (25mm)
below, and 3" (76mm) above the vent to
combustibles.
Center of Rear Vent
30-3/4"
781mm
864 31K