4.3.6

System parameters Block diagram 2

9
See the section "Commissioning and maintenance" for a
detailed description on parameter operation
MANAGING
Functions:
− Reads system sensor (SS)
− Controls thermal unit two-way valve (V1)
− Controls system pump (PS)
− Controls DHW pump (PB) instead of the LPG gas solenoid
valve (VLPG)
− Reads storage tank sensor (SB)
− Manages control of mixed zone 2 zone management (ZM)
device via bus. Up to a maximum of 16 devices can be
managed.
Programmable outputs and inputs parameter configuration (*)
(If Par. 97 = 21-22-23-24-25 - Stand alone configuration)
Par.
Description
Parameter setting
No.
Progr.ble
125
3 = DHW pump (**)
outp. 1
Progr.ble
187
4 = System pump (PS)
outp. 5
Progr.ble
128
1 = General pump (V1)
outp. 4
122
Prog Input 7
3 = System sensor (SS)
188
Prog Input 9
1 = DHW sensor (SB)
(*)
Do NOT change the factory setting of parameter 97
(**)
In place of the fuel shut-off valve VPLG
Configuration of parameters for INAIL kit (***)
Par.
Description
Parameter setting
No.
2 = Water pressure
123
Prog Input 8
117
Prog Input 2
3 = Heating flowmeter M01
(***)
An INAIL kit is required for each thermal unit
Terminals No.
M02
16-17-18
M02
9-10-11
M02
13-14-15
M01
9-10
M01
13-14
Terminals No.
M01
27-28
switch
21-22-23
CONFIGURATION OF CASCADED THERMAL UNITS
Configuration
S1 = OFF (not used)
(189) Burner Address = Managing
Configuration of boiler parameters
Par.
Description
No.
73
Boiler Address
147
Number of Units
184
N. active burner in DHW
7
CH Hysteresis
35
DHW mode
135
Mod. Pump Type
136
Mod. pump mode
140
Minimum Flow
Configuration of cascade parameters
Par.
Description
No.
148
Power Mode
152
PwrMode2 Min Power
153
PwrMode2 Hysteresis
84
Module Rotation Interval
74
Emergency mode setpoint
97
Parameter setting
- "Managing" (if the
cascade sensor is used SC)
- "Stand-Alone" (if the
cascade sensor is not used
SC)
Set the total number of
cascaded units (from 2 to
8)
0 to 8 (Number of active
units for DHW production)
7°C
Choose from:
1 = Water heater with probe
2 = Water heater with
thermostat
2 = Grundfos (choose
according to need)
Fixed 90% (according to
need)
5 l/min
Parameter setting
Choose from:
2 = Maximum number of
burners
3 = Minimum number of
burners
4%
40%
5 days
50 (according to need)