Setting parameters of the additional zone

Controls interface
1
255x80 point backlit display (106,4x39,0mm)
2
RESET key: restores normal operations after a safety shut-down
3
MENU key: switches on the main menu
4
ESC key: in menu navigation, it enables you to exit a menu item and go back to the previous
one
5 ÷ 9 Navigation keys ◄, ▼, ●, ►, ▲
10
Main switch (placed on the rear panel of the equipment)
6.3

Setting zone parameters (accessible only with installer password)

Menu → "Settings" → "Zone Config."
This menu allows you to separately set the parameters of all the connected zones with the exception of the "Extra setpoint zone"
which is the same for all zones.
To select the zone for controlling/changing the parameters, proceed as follows:
− press the ► key so that the number to the right of "zone" is highlighted;
− once the number is highlighted use the ▲ and ▼ keys to change the number of the zone;
− once the zone is selected, confirm with the ● key.
The zone parameters are the following:
Description
Post-circ. Zone Pump
Mix Valve Max Op/Cl Time
Mix Valve Max steps
PID zone mode
PID P Zone
PID I Zone
PID D Zone
Extra zone setpoint
1
2
3
Standard value that is set
120
25
700
Symmetrical
10
150
0
10
4
5
6
7
8
Range
Establishes the time in seconds of the
0-255
Fixes the time in second of the total
0-255
opening/closing of the mix valve (valid
for three point mix valve)
Fixes the number of steps for the total
0-65535
opening of the mix valve (valid for
step-by-step mix valve)
Symmetrical/
Fixes the PID control mode
Asymmetrical
Proportional parameter for the valve
0-255
integrativee parameter for the valve
0-255
Derivative parameter for the valve
0-255
Establishes the increase for the pri-
0-30
mary setpoint with respect to the zone
135
MANAGING ADDITIONAL ZONE
9
10
Explanation
post-circulation
control
control
control
setpoint
UM
Secs
Secs
°C