4. Troubleshooting Guide

Trouble Condition
False Low battery
(ac power
connected before
backup battery
activated)
Low battery
Fault: Smoke
Sensor Error
Fault: Memory Error
End of Unit Life
If you require further information please contact Product Support at 1-800-880-6788 or write us at:
Kidde, 1016 Corporate Park Drive, Mebane, NC 27302. Our internet address is www.kidde.com.
Visual Indications
Amber LED blinks
every 5 sec.
AC Power: Amber LED
blinks every 5 sec.
DC Power: Amber LED
blinks every 60 sec.
AC Power:
Amber LED
blinks every
5 sec.
DC Power:
Amber LED
blinks every
30 sec.
AC Power: Amber LED
blinks twice every
5 sec.
DC Power: Amber
LED blinks twice every
30 sec.
Audible Indications
Chirp every 60 sec, voice "Low
Battery."
Chirp and voice "Low Battery"
every 60 sec. (After 1 hour on DC
power, voice occurs only once
every 15 mins.)
Voice "Hush mode activated" after
button push (first 7 days only).
Chirp every 30 sec, voice "Smoke
Sensor Error" every 60 sec.
(After 1 hour, voice only after
button is pushed.)
Chirp every 30 sec, voice "Memory
Error" every 60 sec.
(After 1 hour, voice only after
button is pushed.)
Chirp twice every 30 sec, with
voice "Replace Alarm." (After 1
hour on DC power, voice occurs
only once every 15 mins.)
Voice "Hush mode activated" after
button push (first 7 days only).
Action
* Pull battery tab to activate
backup battery.
* Push Test/Hush button once
to silence for 24 hrs.
* Replace battery as soon as
possible.
Note: 7 days after Low
Battery begins, the
notifications cannot be
silenced.
* See Cleaning Your Alarm
section.
* Push Test/Hush button once
to attempt to reset the unit.
* If error continues, remove,
dispose unit, and replace as
soon as possible.
* Push Test/Hush button once
to attempt to reset the unit.
* If error continues, remove,
dispose unit, and replace as
soon as possible.
* Push Test/Hush button
once to silence for 24 hrs.
Note: 7 days after End of Unit
Life begins, the
notifications cannot be
silenced.
* Remove, dispose unit, and
replace as soon as possible.
7