McQuay MWMX 010FR Instruction Manual page 27

Dc inverter wall mounted
Table of Contents

Advertisement

4) After evacuation, unscrew the spindle (diagram B) for the gas to run to indoor unit.
Additional Charge
The refrigerant gas is charged in the outdoor unit and, if the piping length is less than 7.6m, additional
charge of the refrigerant after vacuuming is not necessary.
When the piping length is more than 7.6m, please use the table below :
Additional charge per meter
Model
R410A
MWMX 010/015 FR
20g / m