Automatic fire detectors
Hide thumbs Also See for Sinteso S-LINE FDOOT241-9:

Advertisement

Properties
Features
Resistant to environmental and interfering influences such as dust, fibers, insects,
moisture, extreme temperatures, electromagnetic interference, corrosive vapors,
vibration, artificial aerosols, and atypical fire phenomena
Shock resistant, theft protection as an accessory
Time and process-dependent detection behavior
Proven immunity to faults in power electronics
Protected electronics, high-quality components
Sophisticated sensors and electronic monitoring
Internal alarm indicator (IAI), 360° visibility, alignment not necessary
Integrated line separator
'One-man' testing, commissioning, diagnostics, and maintenance
Exchange the detector without resetting the parameters
Exchange the detector without a ladder at heights up to 8 m
Ecological benefits
Environmentally friendly processing
Reusable materials
Electronic parts and synthetic materials can be easily separated
Environmentally friendly detector-testing without gas
Use
Multi-sensor fire detector FDOOT241-9
¹
FS20 compatibility in FDnet is assured subject to in-country FS20 software support.
2
Building Technologies
Fire Safety
Point detector with additional heat sensors
Optional detector dust cap to protect the point detector during the
construction phase
Function
Functions according to the scattered light principle with two sensors: Optical
forward and backward scattering
Opto-electronic measuring chamber: Obstructs disruptive extraneous light
but can be relied upon to detect both light and dark smoke particles
Two additional heat sensors increase the fire detector's immunity to
deceptive phenomena.
Can be set as a multi-sensor smoke detector, smoke detector, or heat
detector by the software
Selectable detection behavior thanks to application-specific ASA parameter
sets
Multi-protocol: Collective / GMT (Cerberus / Siemens) / SynoLINE300,
FDnet
Use
For early detection of flaming fires of solid and liquid substances as well as
of smoldering fires
For early and reliable fire detection in an environment with deceptive
phenomena
Can be used addressed, for the gradual modernization of: