Multi-sensor fire detector FDOOT241-A
Smoke detector FDO241
Heat detector FDT241
Building Technologies
Fire Safety
Point detector with additional heat sensors
Optional detector dust cap to protect the point detector during the
construction phase
Function
Functions according to the scattered light principle with two sensors: Optical
forward and backward scattering
Opto-electronic measuring chamber: Obstructs disruptive extraneous light
but can be relied upon to detect both light and dark smoke particles
Two additional heat sensors increase the fire detector's immunity to
deceptive phenomena.
Can be set as a multi-sensor smoke detector, smoke detector, or heat
detector by the software
Selectable detection behavior thanks to application-specific ASA parameter
sets
Use
For early detection of flaming fires of solid and liquid substances as well as
of smoldering fires
For early and reliable fire detection in an environment with deceptive
phenomena
Can be used addressed
Optional detector dust cap to protect the point detector during the
construction phase
Function
Functions according to the scattered light principle with one sensor: Optical
forward scattering
Opto-electronic measuring chamber: Obstructs disruptive extraneous light
but can be relied upon to detect both light and dark smoke particles
Selectable detection behavior thanks to application-specific ASA parameter
sets
Use
For early detection of flaming fires as well as smoldering fires
Can be used addressed
Optional detector dust cap to protect the point detector during the
construction phase
Function
Two heat sensors prevent the total failure of the thermal detection capacity
of in the event of a fault affecting a sensor.
Measures the operating temperature and the temperature inside the
detector housing so that temperature rise can be detected.
Selectable detection behavior thanks to application-specific ASA parameter
sets
Use
For monitoring rooms in which rapid temperature rise is to be expected in
the event of a fire or if optical detection is difficult
Can be used addressed
3
007005_ad_en_--
2019-01-22