Download Print this page

Danfoss iC7 Installation Manual page 19

Automation frequency converters
Hide thumbs Also See for iC7:

Advertisement

iC7-Automation Frequency Converters
Installation Guide
FK06–FK08
Illustration 15:
Danfoss A/S © 2022.05
L1, L2, L3 / U, V, W
2
FK06
50 mm (1 AWG)
2
FK07
95 mm (3/0 AWG)
2
FK08
120 mm (4/0 mcm)
-DC, R-, +DC/R+
2
FK06
50 mm (1 AWG)
2
FK07
50 mm (1 AWG)
2
95 mm (3/0 AWG)
FK08
BUS
WARN
READY
FAULT
L1, L2, L3
FK06
U, V, W
-DC, R-, +DC/R+
L1, L2, L3
FK07
U, V, W
-DC, R-, +DC/R+
L1, L2, L3
FK08
U, V, W
-DC, R-, +DC/R+
FK06–FK07
T30
FK08
T30/T50
2
16 mm (6 AWG)
2
35 mm (2 AWG)
2
50 mm (1 AWG)
2
16 mm (6 AWG)
2
16 mm (6 AWG)
2
35 mm (2 AWG)
AN319740057641en-000301 / 136R0242 | 19
Instructions
14 Nm (124 in-lb)
14 Nm (124 in-lb)
14 Nm (124 in-lb)
14 Nm (124 in-lb)
14 Nm (124 in-lb)
14 Nm (124 in-lb)
20 Nm (177 in-lb)
20 Nm (177 in-lb)
14 Nm (124 in-lb)
2 Nm (18 in-lb)
10 mm