Summary of Contents for Acromag microBlox Series
Page 1
Technology microBlox® Input Modules USER’S MANUAL ACROMAG INCORPORATED Tel: (248) 295-0880 30765 South Wixom Road Fax: (248) 624-9234 Wixom, MI 48393-2417 U.S.A. email: sales@acromag.com Copyright 2018, Acromag, Inc., Printed in the USA. 8501079B Data and specifications are subject to change without notice.
This is very important where property loss or human life is involved. It is important that you perform satisfactory overall system design and it is agreed between you and Acromag, this is your responsibility. The information of this manual may change without notice. Acromag makes no warranty of any kind with respect to this information, including, but not limited to, the implied warranties of merchantability and fitness for a specific purpose.
Page 4
CE and ATEX / IECEx compliant, and UL approved for installation in Class I, Division II hazardous locations. Acromag, Inc. Tel: 248-295-0880 - 4 - - 4 - https://www.acromag.com...
CISPR 16. Low Voltage AC Mains Port, per CISPR 16. • Installation Category - Suitable for installation in a Pollution Degree 2 environment with an Installation Category (Over-voltage Category) II rating per IEC 1010-1 (1990). Acromag, Inc. Tel: 248-295-0880 - 5 - - 5 - https://www.acromag.com http://www.acromag.com...
WARNING: IEC Safety Standards may require that this device be mounted within an approved metal enclosure or sub-system, particularly for applications with exposure to voltages greater than or equal to 75VDC or 50VAC. Acromag, Inc. Tel: 248-295-0880 - 6 - - 6 - https://www.acromag.com...
DIN rail spring clip down, while pulling the bottom of the carrier outward until it disengages from the rail. Then simply tilt the carrier upward to lift it off the rail. Acromag, Inc. Tel: 248-295-0880 - 7 - - 7 - https://www.acromag.com...
As a rule, input wires are normally separated from power, output, and relay wiring for safety and isolation support, as well as for low noise pickup. Isolation Barriers uBTA-H-1MR Shown or uBTA-H-1SR Acromag, Inc. Tel: 248-295-0880 - 8 - - 8 - https://www.acromag.com http://www.acromag.com...
1005-220 or 1005-221, as shown. Acromag, Inc. Tel: 248-295-0880 - 9 - - 9 - https://www.acromag.com...
Page 10
DIN rail (Acromag part 1027-222 not shown but included in XTBUS-KIT). IMPORTANT - Fusing: It is recommended that supplies capable of delivering more than 2.5A of power to the carrier (or bussed carriers) be fused with a surge tolerant fuse.
(always be sure to also include inductive load protection at your load as shown on the next page): Acromag, Inc. Tel: 248-295-0880 - 12 - - 12 - https://www.acromag.com...
It also helps protect and extend the life of the relay contacts or the switch controlling the load. For more information on this protection, please refer to Acromag Application Note 8501-088 available for download at www.acromag.com. Acromag, Inc. Tel: 248-295-0880...
1-5V, not 0-5V). The Agility App can also scale this for you if you select 4-20mA as an output type option under the uBTA Alarm tab. Acromag, Inc. Tel: 248-295-0880 - 14 - - 14 - https://www.acromag.com...
Agility mobile app and a Bluetooth wireless technology link to your Android or iOS smartphone or tablet. The Agility software can be downloaded free of charge from our web site at www.acromag.com. Quick Overview The screen at left is the uBTA Alarm configuration screen of the Agility mobile app.
Of course, doing it this way would not additionally compensate for any potential module offset of up to ±0.05% or ±2.5mV between different calibrated modules in the same carrier socket. Acromag, Inc. Tel: 248-295-0880 - 16 - - 16 - https://www.acromag.com...
Bluetooth wireless - Carriers also drive voltage and technology link to the module from a smartphone or tablet using the Acromag current transmitter outputs. Agility mobile app. The carrier includes separate analog output terminals for...
Optionally, for transmitter-only operation, fixed range uB models with 0-5V output may be used to convert their output voltage to output current on this carrier. Acromag, Inc. Tel: 248-295-0880 - 19 - - 19 - https://www.acromag.com http://www.acromag.com...
Acromag has automated test equipment that thoroughly checks and calibrates the performance of each unit, and can restore or update firmware if needed. Please refer to Acromag’s Service Policy and Warranty Bulletins, or contact Acromag for complete details on how to obtain repair or replacement.
Two 1027‐222 End Stops for 35 mm DIN Rail mounting For hazardous location installations (Class I, Division 2 or ATEX / IECEx Zone 2), you can use two end stops (Acromag 1027‐222) to help secure modules to 35mm DIN rail (not shown).
Bluetooth wireless technology- Housing w/Mechanical Relays. enabled modules of the microBlox® I/O family. The model “uB” prefix denotes these as members of the Acromag microBlox® uBTA-H-1SR: Single Trx/Alm in family, while “TA” denotes Transmitter/Alarm (“TX” is Transmitter only model), Housing w/Solid-State Relays.
0-5V output and 0-20mA on the carrier. Note that transmitter outputs share a common connection. Acromag, Inc. Tel: 248-295-0880 - 23 - - 23 - https://www.acromag.com...
Alarm functionality of alarm carriers (uBTA-H-1x) can only be configured via a Bluetooth wireless technology connection from an Android or iOS smartphone or tablet and the Acromag Agility mobile app to your specific uB model. Alarm Operating Types Dual Limit: Limit alarms have a high/low set-point applied to the input and assigned to a relay.