TIF Series
Multi-Function Batching Paddle Wheel Flow Meter
Programming Relay Output
STEPS
Press and Hold
1
+
OP2 Output
2
Pulse Control (Frequency)
Pulse Relay
3
Hysteresis
4
Time Delay
5
Relay Selection Mode
ALT NO.
CV > SV ▶ ON: CV < SV - HyS ▶ OFF "Normally Closed Relay"
ALt = 0
CV < SV ▶ ON: CV > SV + HyS ▶ OFF "Normally Open Relay"
ALt = 1
SV + HyS > CV > SV - HyS ▶ ON: CV > SV + HyS or CV < SV - HyS ▶ OFF
ALt = 2
SV + HyS > CV > SV - HyS ▶ OFF: CV > SV + HyS or CV < SV - HyS ▶ ON
ALt = 3
HyS = Hysteresis — Acts like a buffer ± around pulse output (measured in GPM)
CV: Current Value = Flow Rate | SV = Selected or Programmed Value
Min | Max Flow Rates
PIPE SIZE
½" | DN15
¾" | DN20
1" | DN25
1½" | DN40
2" | DN50
23-0069
DISPLAY
SET
��
3 Sec .
Description
GPM
LPM
1.0 | 3.5
32 | 120
1.5 | 5
45 | 170
2.5 | 9
79 | 300
6.5 | 25
225 | 850
10.5 | 40
357 | 1350
Home Screen
Con = n: OP2 Manual Reset (Press
CV < SV: Relay 2 on (OP2 on)
CV < SV: Relay 2 off (OP2 off)
Refer to Relay Selection Mode Below
Press
to change
Press
to save
(Hysteresis is a buffer around the programmed set point)
Reset Flow Totalizer
Press
flow totalizer.
PIPE SIZE
3" | DN80
4" | DN100
6" | DN150
8" | DN200
OPERATION
for 3 sec to reset)
STR
+
keys for 3 seconds to reset the
GPM
LPM
24 | 90
739 | 2800
33 | 125
1149 | 4350
60 | 230
1997 | 7590
82 | 315
2735 | 10395