M-system R8-NC3 Instruction Manual page 7

Power/network module

Advertisement

■ I/O DATA
• Analog Data
0 to 100% of the selected I/O range is converted into 0 to 10000 (binary).
Negative values are represented in 2's complements.
15
•   Pulse Data (32-bit data)
32-bit binary data is used for pulse data.
Lower 16 bits are allocated a lower address and higher 16 bits are allocated a higher address.
32-bit data cannot be accessed using floating addresses.
15
+0
15
+1
•   Analog Data (Temperature date)
15
16-bit binary data is used for temperature data.
With °C, K temperature unit, raw data is multiplied by 10. For example, 25.5°C is converted into 255.
With °F temperature unit, the integer section of raw data is directly converted into the data.
For example, 135.4°F is converted into 135.
Minus temperature is converted into negative values, represented in 2's complements.
• Discrete Data
15
0 : OFF
1 : ON
For I/O mixed modules shown below, interlock status is assigned to input 1 (to 3) in addition to output 1 to 16.
R8-DCM16ALZ
Input 1
R8-DCM16ALK
Input 1
Input 2
Input 3
R8-DCM16ALH
Input 1
Input 2
Input 3
0
0
Lower 16 bits
0
Higher 16 bits
0
0
Input 1 (Output 1)
Input 2 (Output 2)
Input 3 (Output 3)
Input 16 (Output 16)
Full interlock
Full interlock
Individual interlock 1
Individual interlock 2
Full interlock
Partial interlock 1
Partial interlock 2
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: + 81 ( 6 ) 6659-8201 Fax: + 81 ( 6 ) 6659-8510 E-mail: info@m-system.co.jp
:
R8-NC3
EM-9726 P. 7 / 7