Field Set Up And Verification - Carrier AquaEdge 19XR Start-Up, Operation And Maintenance Instructions Manual

Single stage and two-stage semi-hermetic centrifugal liquid chillers with pic 6 controls and r-134a/r-513a 50/60 hz
Table of Contents

Advertisement

(Main MenuConfiguration MenuGeneral [for all Starter/VFD options])
PARAMETER
DEMAND LIMIT TYPE
PULLDOWN RAMP TYPE
DEMAND LIMIT SOURCE
NOTE: Other parameters in this menu are normally left at the default settings; they may be changed as required.
PARAMETER
ECO LBP VLV OPTION
ECO LBP BYPASS VLV LIMIT
DSH DEADBAND FOR LBP
ECO LBP VLV EVAP APPROACH
DYNAMIC DEMAND LIMIT (DDL)
IGNORE DDL TIME
LCW AT SELECTION POINT
LCDW AT SELECTION POINT
100% LIFT DEMAND LIMIT
MIDDLE LIFT PERCENT
MIDDLE LIFT DEMAND LIMIT
20% LIFT DEMAND LIMIT

Field Set Up and Verification

IMPORTANT: Some parameters are specific to the chiller
configuration and will need to be verified prior to operation.
All command functions must be initiated from the HMI.
Use the HMI touch screen to confirm that the configuration
values match the chiller parameter labels and Chiller Builder
design data sheet. See typical jobsite parameters in Tables 8
and 10. Different service tables will need to be checked based
on starter selection.
LABEL LOCATIONS
Verify the following labels have been installed properly and
match the chiller requisition:
Surge Parameters — Located inside the chiller control panel.
Chiller identification nameplates — Located on the right
side of the control panel. A unit-mounted VFD alternate
information nameplate will have two additional labels.
(See Fig. 27.)
- External Machine Electrical Nameplate — located right
side of the VFD (See Fig. 28).
- Internal Machine Electrical Nameplate — located on
the inside of the left VFD enclosure door.
STARTER/DRIVE PROTECTION AND OTHER INCOMING
WIRING
1. Verify that the branch disconnects or other local discon-
nects are open and properly tagged out.
2. Verify that the branch circuit protection and AC input wir-
ing to the starter are in accordance with NEC/CEC
(National Electrical Code/California Energy Commission)
and all other local codes.
3. Verify that the fuses are per the field wiring diagram.
Table 10 — Typical Job Site Parameters
GENCONF - 0=Base Demand, 1=4-20mA
GENCONF - 0=Temperature, 1= Load
GENCONF - 0=Amperes, 1= kW
Table 11 — Typical Job Site Parameters (19XRC)
(Main MenuConfiguration MenuLow Load)
LQBP - Disable/Enable
LQBP - 100%
LQBP - 2^F
LQBP - 5^F
Disable/Enable
30 min (default)
45°F (default)
95°F (default)
100% (default)
60% (default)
80 (default)
45% (default)
TABLE
TABLE
4. Verify that the incoming source does not exceed the SCCR
(short circuit current rating) of the equipment marking.
5. Verify the power lugs in the starter/VFD and branch pro-
tection are properly secured. Inspect the ground cable and
ensure it is properly connected at the branch and to the
ground lug in the starter.
6. Verify the conduit for the power wiring in securely con-
nected to the starter flanged cover and runs continuously
to the branch protection.
7.
Ensure the control and signal wires connected to the chiller
controller or the starter/VFD are in separate conduits.
FINE TUNING VPF (VARIABLE PRIMARY FLOW)
SURGE PREVENTION
Figures 29-32 show how the parameters defined below will af-
fect the configured surge line. The menu can be found under
MAIN MENU  CONFIGURATION MENU  SURGE
CORRECTION CONFIG.
NOTE: Before tuning surge prevention, check for VFD speed
limitation or capacity overrides. If the source of low capacity is
found in one of these places, do not proceed with an attempt to
tune the Surge Prevention configurations.
If capacity is not reached
and
1. ACTUAL GUIDE VANE POSITION < GUIDE VANE
TRAVEL RANGE
and
2. SURGE PREVENTION ACTIVE = YES (can be identi-
fied in MAIN MENU  MAINTENANCE MENU 
SURGE CORRECTION)
and
3. PERCENT LINE CURRENT < 100%
then the surge line is probably too conservative.
31

Advertisement

Table of Contents
loading

Table of Contents