Chiller Dehydration; Inspect Water Piping; Check Relief Valves; Check The Optional Pumpout Compressor Water - Carrier AquaEdge 19XR Start-Up, Operation And Maintenance Instructions Manual

Single stage and two-stage semi-hermetic centrifugal liquid chillers with pic 6 controls and r-134a/r-513a 50/60 hz
Table of Contents

Advertisement

Chiller Dehydration

Dehydration is recommended if the chiller has been open for a
considerable period of time, if the chiller is known to contain
moisture, or if there has been a complete loss of chiller holding
charge or refrigerant pressure.
CAUTION
Do not start or megohm-test the compressor motor or oil
pump motor, even for a rotation check, if the chiller is un-
der dehydration vacuum. Insulation breakdown and severe
damage may result if voltage is applied to the motor.
WARNING
Starters must be disconnected by an isolation switch before
placing the machine under a vacuum. To be safe, isolate
any starter before evacuating the chiller if you are not sure
if there are live leads to the hermetic motor.
Dehydration can be done at room temperatures. Using a cold
trap (Fig. 20) may substantially reduce the time required to
complete the dehydration. The higher the room temperature,
the faster dehydration takes place. At low room temperatures, a
very deep vacuum is required to boil off any moisture. If low
ambient temperatures are involved, contact a qualified service
representative for the dehydration techniques required.
Fig. 20 — Dehydration Cold Trap
Perform dehydration as follows:
1. Connect a high capacity vacuum pump (5 cfm [.002 m
or larger is recommended) to the refrigerant charging
valve (Fig. 3-5). Tubing from the pump to the chiller
should be as short in length and as large in diameter as
possible to provide least resistance to gas flow.
2. Use an absolute pressure manometer or a digital vacuum
gage to measure the vacuum.
3. If the entire chiller is to be dehydrated, open all isolation
valves (if present).
4. With the chiller ambient temperature at 60F (15.6C) or
higher, operate the vacuum pump until the manometer
reads 29.72 in. Hg (vac) (754.9 mm Hg), or a vacuum
indicator reads 35F (1.7C). Operate the pump an addi-
tional 2 hours.
Do not apply a vacuum greater than 29.73 in. Hg (vac)
(755.1 mm Hg) or go below 33F (0.56C) on the wet bulb
vacuum indicator. At this temperature and pressure, isolated
pockets of moisture can turn into ice. The slow rate of evap-
oration (sublimation) of ice at these low temperatures and
pressures greatly increases dehydration time.
5. Valve off the vacuum pump, stop the pump, and record the
instrument reading.
6. After a 2-hour wait, take another instrument reading. If the
reading has not changed, dehydration is complete. If the
reading indicates vacuum loss, repeat Steps 4 and 5.
7.
If the reading continues to change after several attempts,
perform a leak test up to the maximum 160 psig (1103 kPa)
pressure. Locate and repair the leak, and repeat dehydration.
8. Once dehydration is complete, the evacuation process can
continue. The final vacuum prior to charging the unit with
refrigerant should in all cases be 29.9 in. Hg (500 microns,
0.07 kPa [abs]) or less.

Inspect Water Piping

Refer to piping diagrams provided in the certified drawings
and the piping instructions in the 19XR Installation Instruc-
tions manual. Inspect the piping to the cooler and condenser.
Be sure that the flow directions are correct and that all piping
specifications have been met.
Piping systems must be properly vented with no stress on wa-
terbox nozzles and covers. Water flows through the cooler and
condenser must meet job requirements. Measure the pressure
drop across the cooler and the condenser.
Water must be within design limits, clean, and treated to en-
sure proper chiller performance and to reduce the potential
of tube damage due to corrosion, scaling, or erosion. Carrier
assumes no responsibility for chiller damage resulting from
untreated or improperly treated water.

Check Relief Valves

Be sure the relief valves have been piped to the outdoors in
compliance with the latest edition of ANSI/ASHRAE Standard
15 and applicable local safety codes. Piping connections must
allow for access to the valve mechanism for periodic inspec-
tion and leak testing.
The standard 19XR relief valves are set to relieve at 185 psig
(1275 kPa) chiller design pressure.

Check the Optional Pumpout Compressor Water

Piping

If the optional pumpout storage tank and/or pumpout system
are installed, check to ensure the pumpout condenser water has
/s]
3
been piped in. Check for field-supplied shutoff valves and con-
trols as specified in the job data. Check for refrigerant leaks on
field-installed piping.

Identify and Check Starter/VFD

Verify that the starter/VFD in submittal paperwork matches the
actual starter/VFD on the jobsite. Typical design characteristic
is for the stater/VFD to be able to operate in the following en-
vironment conditions. In all cases identify the starter by re-
viewing marking/part number on the inside/outside of the start-
er cabinet doors. See Table 7.
Table 7 — Starter/VFD Identification
CONDITION
AMBIENT TEMPERATURE
(OUTSIDE NEMA 1 ENCLOSURE)
STORAGE TEMPERATURE
(AMBIENT)
HUMIDITY
Locate the appropriate wiring diagrams associated with the
identified starter.
25
CAUTION
SPECIFICATION
32 to 104°F (0 to 40°C)
–40 to 149°F (–40 to 65°C)
5% to 95%
(non-condensing)

Advertisement

Table of Contents
loading

Table of Contents