Mounting the reader
The procedure for installing the reader depends on the operating environment or the type of
installation.
NOTICE
Protection class dependent on type of installation
Note that the protection class of the reader depends on the type of installation. If the reader is
installed inside a wall (in-wall installation), the reader has degree of protection IP65 on the
front. If the reader is installed using the table/wall housing on a wall or on a table (surface/table
installation), the reader has degree of protection IP41.
In-wall or cabinet installation
NOTICE
Installation conditions
• The thickness of the wall on which the reader is mounted must be 2-7 mm.
• The installation opening must have the following dimensions: 76.5 (± 0.3) × 48.5 (± 0.3)
Follow the steps below to install the RF1000 reader inside a wall or in a control cabinet:
1. When operating via the RS232 interface:
Replace the pre-installed USB cable with the supplied RS232 cable as described in the section
"Connecting (Page 25)".
2. Optionally when using the cleanroom cover:
Drill condensate holes below the installation opening.
Figure 4-1
SIMATIC RF1000
Operating Instructions, 05/2023, C79000-G8976-C432-10
mm
Condensate holes
Installation