Wiring Diagram: Outdoor Unit - Daikin RXYSQ5T8VB Installation And Operation Manual

System air conditioner
Table of Contents

Advertisement

9 Technical data
9.3

Wiring diagram: Outdoor unit

The wiring diagram is delivered with the unit, located at the inside of
the service cover.
Notes for RXYSQ4~6_V:
1
Symbols (see below).
2
For X37A refer to the installation manual of the option.
3
Refer to the installation or service manual on how to use
BS1~BS5 push buttons, and DS1‑1 and DS1‑2 DIP switches.
4
Do not operate the unit by short-circuiting protection device
S1PH.
5
Refer to the installation manual for indoor-outdoor
transmission F1-F2 wiring.
6
When using the central control system, connect outdoor-
outdoor transmission F1-F2.
Notes for RXYSQ4~6_Y:
1
Symbols (see below).
2
For X37A refer to the installation manual of the option.
3
Refer to the installation or service manual on how to use
BS1~BS4 push buttons, and DS1‑1 and DS1‑2 DIP switches.
4
Do not operate the unit by short-circuiting protection device
S1PH.
5
Refer to the installation manual for indoor-outdoor
transmission F1-F2 wiring.
6
When using the central control system, connect outdoor-
outdoor transmission F1-F2.
Symbols:
X1M
Main terminal
Earth wiring
15
Wire number 15
Field wire
Field cable
**
/12.2
Connection ** continues on page 12 column 2
1
Several wiring possibilities
Option
Not mounted in switch box
Wiring depending on model
PCB
Legend for wiring diagram RXYSQ4~6_V:
A1P
Printed circuit board (main)
A2P
Printed circuit board (filter)
A3P
Printed circuit board (cool/heat selector) (option)
BS*
Push buttons (mode, set, return, test, reset) (A1P)
C1
Capacitor (A1P)
DS1
DIP switch (A1P)
F1U
Fuse (T 56 A / 250 V) (A2P)
F3U, F4U
Fuse (T 6.3 A / 250 V) (A2P)
F6U
Fuse (T 5.0 A / 250 V) (A1P)
H*P
LED (service monitor orange) (A1P)
HAP
Running LED (service monitor green) (A1P)
HBP
Frequency LED (service monitor green) (A1P)
K11M
Magnetic contactor (A1P)
K*R
Magnetic relay (A1P)
Installation and operation manual
26
L*R
Reactor (A1P)
M1C
Motor (compressor)
M1F
Motor (upper fan)
M2F
Motor (lower fan)
PS
Switching power supply (A1P)
Q1DI
Earth leakage circuit breaker (field supply)
R*
Resistor (A1P)
R1T
Thermistor (air)
R2T
Thermistor (discharge)
R3T
Thermistor (suction 1)
R4T
Thermistor (heat exchanger)
R5T
Thermistor (suction 2)
R6T
Thermistor (subcool heat exchanger)
R7T
Thermistor (liquid pipe)
FINTH
Thermistor (fin)
S1NPH
High pressure sensor
S1NPL
Low pressure sensor
S1PH
High pressure switch
S1S
Air control switch (option)
S2S
Cool/heat selector switch (option)
V1R
IGBT power module (A1P)
V2R
Diode module (A1P)
V*T
Insulated gate bipolar transistor (IGBT) N-channel
(A1P)
V*D
Diode (A1P)
X*A
PCB connector
X*M
Terminal strip
X*Y
Connector
X37A
Connector (power supply for option PCB)
Y1E
Electronic expansion valve (main)
Y3E
Electronic expansion valve (subcool heat exchanger)
Y1S
Solenoid valve (4‑way valve)
Z*C
Noise filter (ferrite core)
Z*F (A*P)
Noise filter
Legend for wiring diagram RXYSQ4~6_Y:
A1P
Printed circuit board (main)
A2P
Printed circuit board (inverter)
BS*
Push buttons (mode, set, return, test, reset) (A1P)
C*
Capacitor (A2P)
DS1
DIP switch (A1P)
F1U, F2U
Fuse (T 31.5 A / 500 V) (A1P)
F1U
Fuse (T 5.0 A / 250 V) (A2P)
F3U, F4U,
Fuse (T 6.3 A / 250 V) (A1P)
F5U
H*P
LED (service monitor orange) (A1P)
HAP
Running LED (service monitor green) (A*P)
K1M
Magnetic contactor (A2P)
K*R
Magnetic relay (A*P)
L1R
Reactor
M1C
Motor (compressor)
M1F
Motor (upper fan)
M2F
Motor (lower fan)
RXYSQ4~6T8V/YB
VRV IV-S system air conditioner
4P482275-1 – 2017.04