Making Field Settings; About Making Field Settings; To Access The Field Setting Components; Field Setting Components - Daikin RXYSQ5T8VB Installation And Operation Manual

System air conditioner
Table of Contents

Advertisement

6.1

Making field settings

6.1.1

About making field settings

To configure the heat pump system, you must give input to the
outdoor unit's main PCB (A1P). This involves the following field
setting components:
▪ Push buttons to give input to the PCB
▪ A display to read feedback from the PCB
▪ DIP switches (only change the factory settings if you install a cool/
heat selector switch).
Field settings are defined by their mode, setting and value. Example:
[2‑8]=4.
PC configurator
For VRV IV-S heat pump system it is alternatively possible to make
several commissioning field settings through a personal computer
interface (for this, option EKPCCAB is required). The installer can
prepare the configuration (off-site) on PC and afterwards upload the
configuration to the system.
See also:
"6.1.9  To connect the PC configurator to the outdoor
unit" on
page 22.
Mode 1 and 2
Mode
Mode 1
Mode 1 can be used to monitor the current
situation of the outdoor unit. Some field setting
(monitoring
contents can be monitored as well.
settings)
Mode 2
Mode 2 is used to change the field settings of
the system. Consulting the current field setting
(field settings)
value and changing the current field setting
value is possible.
In general, normal operation can be resumed
without special intervention after changing field
settings.
Some field settings are used for special
operation (e.g., 1 time operation, recovery/
vacuuming setting, manual adding refrigerant
setting, etc.). In such a case, it is required to
abort the special operation before normal
operation can restart. It will be indicated in
below explanations.
6.1.2

To access the field setting components

See
"5.1.1 To open the outdoor unit" on
6.1.3

Field setting components

The components to make field settings are as follows:
RXYSQ4~6T8V/YB
VRV IV-S system air conditioner
4P482275-1 – 2017.04
Description
page 8.
V
TEST:
MODE
A1P
HWL:
IND
A2P
H1P
H2P
H3P
BS1
BS2
MODE
SET
X1M
X2M
Y
TEST/
MODE
IND
HWL
A2P
A1P
H1P
H2P
H3P
BS1
BS2
MODE
SET
X1M
X2M
DS1
DIP switches
BS1~BS5
Push buttons
H1P~H7P
7‑LEDs display
H8P
LED for indication during initialisation
ON ( ) OFF ( ) Flashing ( )
DIP switches
Only change the factory settings if you install a cool/heat selector
switch.
DS1‑1
COOL/HEAT selector (refer to the manual of the
cool/heat selector switch). OFF=not
installed=factory setting
DS1‑2
NOT USED. DO NOT CHANGE THE FACTORY
SETTING.
Push buttons
Use the push buttons to make the field settings. Operate the push
buttons with an insulated stick (such as a closed ball-point pen) to
avoid touching of live parts.
BS1
MODE: For changing the set mode
BS2
SET: For field setting
BS3
RETURN: For field setting
BS4
TEST: For test operation
BS5
RESET: For resetting the address when the wiring is
changed or when an additional indoor unit is installed
7‑LEDs display
The display gives feedback about the field settings, which are
defined as [Mode-Setting]=Value.
H1P
Shows the mode
H2P~H7P
Shows the settings and values, represented in binary code
H8P
NOT used for field settings, but used during initialisation
Example:
[
-
32
+
16
+
8
+
4
+
2
+
1]
H1P
H1P H2P H3P H4P H5P H6P H7P
(H1P OFF)
(H1P flashing)
(H1P ON)
0
+
0
+
8
+
0
+
0
+
0
(H2P~H7P = binary 8)
6 Configuration
C/H SELECT
L.N.O.P. DEMAND
MULTI
MASTER SLAVE
H4P
H5P
H6P
H7P
H8P
BS3
BS4
BS5
RETURN
TEST
RESET
ON
DS1
OFF
1 2
MASTER
SLAVE
L.N.O.P.
DEMAND
MULTI
H4P
H5P
H6P
H7P
H8P
BS3
BS4
BS5
RETURN
TEST
RESET
ON
DS1
OFF
1 2
Description
Default situation
Mode 1
Mode 2
Setting 8
(in mode 2)
Installation and operation manual
17

Advertisement

Table of Contents
loading

Table of Contents