Carrier K WPG4 Series Installation Instructions Manual page 52

13.4 seer2 single-packaged air conditioner and gas furnace system with r-410a refrigerant single phase 2-5 nominal tons (sizes 24-60) three phase 3-5 nominal tons (sizes 36-60)

Advertisement

PGD4 Series K WPG4 Series K: Installation Instructions
SYMPTOM
No Power or Hardware failure
(LED OFF)
Check fuse, low voltage circuit
(LED 1 flash)
Limit switch faults
(LED 2 flashes)
Flame sense fault
(LED 3 flashes)
4 consecutive limit switch faults
(LED 4 flashes)
Ignition lockout fault
(LED 5 flashes)
Pressure Switch fault
(LED 6 flashes)
Rollout switch fault
(LED 7 flashes)
Internal control fault
(LED 8 flashes)
1
Temporary 1 hr auto reset
(LED 9 flashes)
*WARNING
: If the IGC must be replaced, be sure to ground yourself to dissipate any electrical charge that my be present before handling new control board. The
IGC is sensitive to static electricity and my be damaged if the necessary precautions are not taken.
IMPORTANT: Refer to
Table
14-Troubleshooting Guide-Heating for additional troubleshooting analysis.
LEGEND
IGC—Integrated Gas Unit Controller
LED—Light-Emitting Diode
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
Table 15 – Troubleshooting Guide–LED Status Codes
CAUSE
Loss of power to control module (IGC)*.
Fuse is blown or missing or short circuit in secondary
(24VAC) wiring.
High temperature limit switch is open.
The IGC* sensed flame that should not be present.
Inadequate airflow to unit.
Unit unsuccessfully attempted ignition for 15 minutes.
Open pressure switch.
Rollout switch has opened.
Microprocessor has sensed an error in the software
or hardware.
Electrical interference impeding IGC software
Check 5-amp fuse son IGC*, power to unit, 24-v circuit breaker,
and transformer. Units without a 24-v circuit breaker have an
internal overload in the 24-v transformer. If the overload trips,
allow 10 minutes for automatic reset.
Replace fuse if needed. Verify no short circuit in low voltage (24
VAC wiring).
Check the operation of the indoor (evaporator) fan motor. Ensure
that the supply-air temperature rise is in accordance with the
range on the unit nameplate. Clean or replace filters.
Reset unit. If problem persists, replace control board.
Check the operation of the indoor (evaporator) fan motor and
that supply-air temperature rise agrees with range on unit
nameplate information.
Check ignitor and flame sensor electrode spacing, gaps, etc.
Ensure that fame sense and ignition wires are properly
terminated. Verify that unit is obtaining proper amount of gas.
Verify wiring connections to pressure switch and inducer motor.
Verify pressure switch hose is tightly connected to both inducer
housing and pressure switch. Verify inducer wheel is properly
attached to inducer motor shaft. Verify inducer motor shaft is
turning.
Rollout switch will automatically reset, but IGC* will continue to
lockout unit. Check gas valve operation. Ensure that
induced-draft blower wheel is properly secured to motor shaft.
Inspect heat exchanger. Reset unit at unit disconnect.
If error code is not cleared by resetting unit power, replace the
IGC*.
Reset 24-v. to control board or turn thermostat off, then on again.
Fault will automatically reset itself in one (1) hour.
52