SECTION 2 – INSTALLATION

2.12.1 MASSACHUSETTS INSTALLATIONS

For Massachusetts installations, the following companies provide vent systems which conform
to all applicable requirements for installations within the Commonwealth of Massachusetts.
Contact information is as follows:
Selkirk Corporation - Heatfab Division
130 Industrial Blvd.
Turners Falls, MA 01376
Phone: 1-800-772-0739
www.heatfab.com
Glover Sheet Metal, Inc.
44 Riverdale Ave.
Newton, MA 02485
Phone: (617) 527-8178
www.gloversheetmetal.com

2.13 COMBUSTION AIR

The Benchmark Venting and Combustion Air Guide, TAG-0022 (GF-2050) MUST be consulted
before any inlet air venting is designed or installed. Air supply is a direct requirement of ANSI
223.1, NFPA-54, CSA B149.1 and local codes. These codes should be consulted before a
permanent design is determined.
The combustion air must be free of chlorine, halogenated hydrocarbons, other chemicals that
can become hazardous when used in gas-fired equipment and other combustion products.
Common sources of these compounds are swimming pools, degreasing compounds, plastic
processing, and refrigerants. Whenever the environment contains these types of chemicals,
combustion air MUST be supplied from a clean area outdoors for the protection and longevity of
the equipment and warranty validation.
If combustion air is supplied directly to the unit(s) though air duct(s), see section 2.13.1 below.
If combustion air is not supplied through air ducts, it must be supplied to the unit(s) through two
permanent openings. These two openings must have a free area of not less than one square
2
inch (6.5 cm
) for each 4000 BTUs (1.17 kW) input for each unit. The free area must take
into account restrictions such as louvers and bird screens.
For Canada installations, refer to the requirements specified in CSA B149.1-10, sections 8.4.1
and 8.4.3.
OMM-136_E • GF-210 •
12/13/2019
Technical Support • (800) 526-0288 • Mon-Fri, 8 am - 5 pm EST
Watertown Supply
33 Grove St.
Watertown, MA 02472
Phone: (617) 924-2840
www.watertownsupply.com
Emerson Swan Co
Engineering Products Department
300 Pond St.
Randolph, MA 02368
Phone 781-986-2555
Fax 781-986-2027
www.emersonswan.com
Page 41 of 57