SECTION 2: OPERATION

2.8.2 BMK 1500/2000 COMBUSTION CAL Menus

TABLE 2-7a: COMBUSTION CAL Menu: BMK 1500/2000
SINGLE FUEL – NATURAL GAS
MENU ITEM DISPLAY
CAL Voltage 16%
1
CAL Voltage 18%
2
CAL Voltage 30%
3
CAL Voltage 40%
4
CAL Voltage 50%
5
CAL Voltage 70%
6
CAL Voltage 100%
7
SET Valve Position
8
Blower Output
9
Set Stdby Volt
10
Oxygen Level
TABLE 2-7b: COMBUSTION CAL Menu: BMK 1500/2000
DUAL FUEL
MENU ITEM DISPLAY
CAL Voltage: 16%
1
CAL Voltage: 18%
2
CAL Voltage 30%
3
CAL Voltage 40%
4
CAL Voltage 50%
5
CAL Voltage 70%
6
CAL Voltage 100%
7
SET Valve Position
8
Blower Output
9
Set Stdby Volt
10
Oxygen Level
* The default values for Natural Gas on Dual Fuel units are different than the default values for
Natural Gas on Single Fuel units. These values do NOT apply to single fuel units.
OMM-0122_D • GF-206 • 5/9/2019
MINIMUM
MAXIMUM
0.25
10.00
0.25
10.00
0.25
10.00
0.25
10.00
0.25
10.00
0.25
10.00
0%
100%
0
10.00 V
MINIMUM
MAXIMUM
0.25
10.00
0.25
10.00
0.25
10.00
0.25
10.00
0.25
10.00
0.25
10.00
0.25
10.00
0
100
0
10.0
Technical Support • (800) 526-0288 • Mon-Fri, 8 am - 5 pm EST
BMK 1500
1.80
2.30
2.50
2.90
3.80
7.90
Displays current value
2.00 V
Displays current value
DEFAULT
*
NATURAL GAS
BMK 1500
BMK 2000
1.50
2.10
2.60
4.50
3.20
4.50
3.30
4.50
4.10
4.80
8.30
9.80
Variable
Displays current value
2.00
2.00
Displays current value
DEFAULT
BMK 2000
1.40
3.80
4.30
5.40
6.40
9.50
Variable
2.00 V
PROPANE
BMK 1500
BMK 2000
1.20
2.10
2.30
3.50
2.80
3.90
3.00
4.10
3.50
4.10
7.70
8.90
2.00
2.00
Page 24 of 164