Watts AERCO Benchmark OMM-0121 Operation And Maintenance Manual page 70

Natural gas, propane gas and dual fuel fired modulating & condensing boilers
Table of Contents

Advertisement

Benchmark 750-3000 Boiler Operation & Maintenance Manual
SECTION 5 – TROUBLESHOOTING GUIDE
TABLE 5-1: Boiler Troubleshooting Procedures
Fault
Probable Causes
Indication
SSOV relay failed on IGST board.
1.
Floating Neutral.
SSOV RELAY
2.
FAILURE
3.
Hot and Neutral reversed at SSOV.
Actuator not allowing for full closure of gas
1.
valve.
SSOV powered when it should not be
2.
SSOV
SWITCH OPEN
Defective switch or Actuator.
3.
Incorrectly wired switch.
4.
Air/Fuel Valve out of calibration.
1.
Air/Fuel Valve unplugged.
2.
Loose wiring connection to the stepper motor.
3.
STEPPER
MOTOR
FAILURE
Defective Air/Fuel Valve stepper motor.
4.
Defective Power Supply Board or fuse.
5.
Defective IGST Board.
6.
OMM-0122_D • GF-206 • 5/9/2019
Technical Support • (800) 526-0288 • Mon-Fri, 8 am - 5 pm EST
Corrective Action
Press CLEAR button and restart unit. If fault persists, replace
1.
Ignition/Stepper (IGST) Board.
The Neutral and Earth Ground are not connected at the source and
2.
therefore there is a voltage measured between the two. Normally this
measurement should be near zero or no more than a few millivolts.
3.
Check SSOV power wiring.
Observe operation of the Safety Shut-Off Valve (SSOV) through
1.
indicator on the Valve actuator and ensure that the valve is fully and
not partially closing.
If the SSOV never closes, it may be powered continuously. Close
2.
the gas supply and remove power from the unit. Refer fault to
qualified service personnel.
Remove the electrical cover from the SSOV and check switch
3.
continuity. If the switch does not show continuity with the gas valve
closed, either adjust or replace the switch or actuator.
Ensure that the SSOV Proof of Closure switch is correctly wired.
4.
Refer to the C-More User Manual OMM-0032 (GF-112) and perform
1.
the Stepper Feedback Calibration procedure in Section 6, section
6.2.1.
Check that the Air/Fuel Valve is connected to the C-More Controller.
2.
Inspect for loose connections between the Air/Fuel Valve motor and
3.
the wiring harness.
Replace stepper motor.
4.
Check DS1 & DS2 LEDs on Power Supply Board. If they are not
5.
steady ON, replace Power Supply Board.
Check "Heartbeat" LED DS1 and verify it is blinking ON & OFF
6.
every second. If not, replace IGST Board.
Page 70 of 164

Advertisement

Table of Contents
loading

Table of Contents