Watts AERCO Benchmark OMM-0121 Operation And Maintenance Manual page 30

Natural gas, propane gas and dual fuel fired modulating & condensing boilers
Table of Contents

Advertisement

Benchmark 750-3000 Boiler Operation & Maintenance Manual
SECTION 2: OPERATION
TABLE 2-10: CALIBRATION Menu
MENU ITEM DISPLAY
29
A/F Sensitivity
30
Power Reset
31
Water Temp Reset
32
Gas Press Reset
33
Min Off Time
34
Heatr Tuning Dsp
35
Heatr Bkpt Dsp
36
Stop Level
37
Start Level
38
Skip Range Cntr
39
Skip Range Span
40
Skip Speed
41
O2 Gain
O2 Offset
42
43
O2 Sensor
44
Cal Temp Sensors
45
FFWD Temp Offset
46
Exhst Tmp Offset
47
Outdr Air Offset
48
Inlet Air Offset
49
Inlet Wtr Offset
50
Outlet Wtr Offset
51
24 hr Max Cycles
52
24 hr Max Ovrtemp
53
0-10v Out Test
Spark Monitor
54
55
Min Spark Amps
56
Max Spark Amps
OMM-0122_D • GF-206 • 5/9/2019
AVAILABLE CHOICES OR LIMIT
Minimum
Maximum
1%
Automatic or Manual
Automatic or Manual
Automatic or Manual
0 Min
15 Min
Enabled or Disabled
Enabled or Disabled
0%
Start Level
Stop Level
40%
10
0
0.5
0.500
1.500
-24.0
+2.0
Enabled or Disabled
Off or Start
-20
-20
-20
-20
-20
-20
0
9999
0
9999
0.0
10.0
Enabled or Disabled
0.0 Amps
2.5 Amps
0.0 Amps
2.5 Amps
Technical Support • (800) 526-0288 • Mon-Fri, 8 am - 5 pm EST
5%
95
3
2.0
Depends on unit type/size
+20
+20
+20
+20
+20
+20
Depends on unit type/size
0.10 Amps
0.40 Amps
DEFAULT
2%
Automatic
Automatic
Manual
1 Min
Disabled
Disabled
16
22
40
0%
0.5%
1.000
1.0
Off
0
0
0
0
0
0
0
0
0.00
Page 30 of 164