ABB ARG600 Single SIM Variant User Manual

ABB ARG600 Single SIM Variant User Manual

Wireless gateway
Table of Contents

Advertisement

Quick Links

Wireless Gateway
ARG600 Single SIM Variant
User Manual

Advertisement

Table of Contents
loading

Summary of Contents for ABB ARG600 Single SIM Variant

  • Page 1 — Wireless Gateway ARG600 Single SIM Variant User Manual...
  • Page 3 Document ID: 1MRS758456 Issued: 2022-06-20 Revision: H Product version: 3.4 © Copyright 2022 ABB. All rights reserved...
  • Page 4 Copyright This document and parts thereof must not be reproduced or copied without written permission from ABB, and the contents thereof must not be imparted to a third party, nor used for any unauthorized purpose. The software or hardware described in this document is furnished under a license and may be used, copied, or disclosed only in accordance with the terms of such license.
  • Page 5 ABB is not liable for any such damages and/or losses.
  • Page 6 Safety information Dangerous voltages can occur on the connectors, even though the auxiliary voltage has been disconnected. Non-observance can result in death, personal injury or substantial property damage. Only a competent electrician is allowed to carry out the electrical installation. National and local electrical safety regulations must always be followed.
  • Page 7: Table Of Contents

    Connection principle..............21 Logging in..................22 User interface................22 Setting Ethernet port function to LAN..........22 Configuring mobile WAN..............23 Configuring the default route............23 Section 5 Network configuration.............25 Defining host and domain names............. 25 ARG600 Single SIM Variant User Manual...
  • Page 8 Modbus Gateway properties.............43 Modbus mode...................44 Configuring the network master to serial slaves mode.....45 Parameter settings................45 Section 11 Troubleshooting..............49 Common troubleshooting issues............49 Viewing the system log..............49 Section 12 Technical data..............51 Section 13 Glossary................. 55 ARG600 Single SIM Variant User Manual...
  • Page 9: Section 1 Introduction

    The personnel is expected to be familiar with basic working principles of Internet technology. Product documentation 1.3.1 Product documentation set Product series- and product-specific manuals can be downloaded from the ABB Web site abb.com/mediumvoltage. 1.3.2 Document revision history Document revision/date...
  • Page 10: Related Documentation

    3G/LTE Wireless Gateway firmware Updating firmware of Wireless 1MRS758451 update Technical Note Gateway devices Product series- and product-specific manuals can be downloaded from the ABB Web site abb.com/mediumvoltage. Symbols and conventions 1.4.1 Symbols The electrical warning icon indicates the presence of a hazard which could result in electrical shock.
  • Page 11: Document Conventions

    • Parameter names are shown in italics. The function can be enabled and disabled with the Operation setting. • Parameter values are indicated with quotation marks. The corresponding parameter values are "On" and "Off". ARG600 Single SIM Variant User Manual...
  • Page 13: Section 2 Arg600 Overview

    Wireless Gateway ARG600 exhibits integrated communication capability and seamless integration to the SCADA systems. Wireless Gateway ARG600 is a member of ABB’s Arctic product family and part of its 600 Wireless Gateway product series. By using Wireless Gateway ARG600, Ethernet and serial devices can be attached to a TCP/IP based control system.
  • Page 14: Physical Interfaces

    IEC 60950-1 2 Console/serial port 3 Application serial ports 4 LAN/WAN port 5 Power switch 6 Console/serial port switch 7 DIP switches Power supply connector The device has a VDC power supply connector. ARG600 Single SIM Variant User Manual...
  • Page 15 The DIP switches select an application port (RS2) mode and settings (RS-232 or RS-485). By default, all DIP switches are set to the 0 position (RS-232 mode). DIP switches 2...4 apply only when DIP switch 1 is set to differential mode (RS-485/ RS-422). ARG600 Single SIM Variant User Manual...
  • Page 16: Back Panel

    The device has an RJ-45 connector for 10/100 Mbps Ethernet connection. The maximum length of the Ethernet cable is 100 m. 2.2.2 Back panel The device has an antenna connector and a slot for a SIM card on the back panel. ARG600 Single SIM Variant User Manual...
  • Page 17: Side Panel

    Side panel The ten LEDs on the side panel of the device indicate the status of the device. Only five of them are connected. The LEDs are numbered 1...10 starting from the rear panel side. ARG600 Single SIM Variant User Manual...
  • Page 18 Ethernet link is transferring data Ethernet link down Eth 2 LED reserved for future use Led 1 LED reserved for future use Led 2 LED reserved for future use Table continues on next page ARG600 Single SIM Variant User Manual...
  • Page 19: Din Rail Mounting

    Ethernet MAC address. Firmware version The device's firmware version is visible on the welcome page (System/Welcome Page), which is displayed after logging in to the device. For firmware updates, contact ABB's technical customer support. ARG600 Single SIM Variant User Manual...
  • Page 21: Section 3 Physical Connections

    The baud rate is fixed to 115200 bps when the port is configured in the serial console mode. GUID-9F6668AA-EBAB-46B5-A1AF-35D8AE3E6C12 V1 EN-US Figure 5: Console/RS1 port connector Table 3: Console/RS1 port pinout Function Table continues on next page ARG600 Single SIM Variant User Manual...
  • Page 22: Serial Port 2

    Serial port 2 Serial port 2 can be configured to multiple serial formats (RS-232/422/485). The default is RS-232. GUID-9F6668AA-EBAB-46B5-A1AF-35D8AE3E6C12 V1 EN-US Figure 6: Application serial port Table 5: Application serial port pinout (RS-232) Function ARG600 Single SIM Variant User Manual...
  • Page 23 RS-232 mode. This could damage the port and the connected equipment. Table 8: Application serial port pinouts in RS-422/485 modes RS-422 full-duplex (4-wire) RS-485 half-duplex (2-wire) RXD positive (in) TXD negative (out) TXD/RXD negative (out/in) Table continues on next page ARG600 Single SIM Variant User Manual...
  • Page 24: Ethernet

    GPRS, 3G or LTE frequency bands. The antenna is connected directly to the connector located on the device's back panel. Commercially available antennas are usually provided with a flexible 50 Ω cable with a length of 2...3 meters and a male type SMA connector. ARG600 Single SIM Variant User Manual...
  • Page 25 Section 3 1MRS758456 H Physical connections If the PIN code query is enabled, check that the ARG600 configurator has the correct PIN code entered in the wireless WAN submenu. ARG600 Single SIM Variant User Manual...
  • Page 27: Section 4 Getting Started

    WAN automatically receives traffic if the other one goes down. For example, if the primary Ethernet connection goes down, the traffic is automatically switched to mobile WAN (secondary connection) and back when the Ethernet interface comes up again. ARG600 Single SIM Variant User Manual...
  • Page 28: Logging In

    DHCP discovery fails, the device automatically uses IP address 10.10.10.10. Change the following setting before changing any other Ethernet settings. In the left pane, under Network, click Ethernet Port. Set Port function to LAN. Click Submit to save the settings. ARG600 Single SIM Variant User Manual...
  • Page 29: Configuring Mobile Wan

    WAN, set Interface to Mobile WAN or Ethernet WAN, whichever is not selected as the default gateway. If the primary WAN interface comes down, the device automatically switches the default route to the backup WAN interface. Click Submit to save the settings. Restart the device. ARG600 Single SIM Variant User Manual...
  • Page 31: Section 5 Network Configuration

    WAN switch logic to try the secondary interface. 5.2.3 Configuring the mobile WAN interface Set Enable to Yes. If the SIM card is protected by a PIN code, enter the code in the PIN Code field. ARG600 Single SIM Variant User Manual...
  • Page 32: Setting Wan Failover And Backup Routing

    If the backup WAN interface needs to come up only when the primary interface goes down, select Yes. • If both the wireless and Ethernet WAN interfaces have to be up all the time, select No. Click Submit to save the settings. Restart the device. ARG600 Single SIM Variant User Manual...
  • Page 33: Routing Parameters

    Default route OpenVPN. See OpenVPN application note. Configuring the network monitor The network monitor detects Internet connectivity drops by sending ping packets to designated targets. Its use is recommended. ARG600 Single SIM Variant User Manual...
  • Page 34: Configuring Dns Proxy

    In the left pane, under System, click Status to view network status information. In the left pane, under Tools, click Modem Info to view the status of the wireless modem. Check if the cellular LED is flashing, indicating network traffic. ARG600 Single SIM Variant User Manual...
  • Page 35: Section 6 Serial Port Configuration

    Because of the transparent communication, any protocols can be used in actual communication between nodes.Serial gateway configuration depends on used protocols. ARG600 Single SIM Variant User Manual...
  • Page 37: Section 7 Additional System Configuration

    In the “Manual” mode, enter the time and date in the Time and Date fields, respectively. Clicking Copy PC changes the device’s time and date settings to match the connected PC. This requires JavaScript support from the browser. Click Submit to save the settings. ARG600 Single SIM Variant User Manual...
  • Page 38: Restoring Factory Default Settings

    Selecting Last Boot allows saving the configuration in use when the device was booted the previous time. Type a name for the profile. Click Submit to save the profile. It is possible to clone, export, and import profiles in the same view. ARG600 Single SIM Variant User Manual...
  • Page 39: Section 8 Service Configuration

    Selects which SSH protocol versions are enabled in SSH SSH1, SSH2 version Server. It is recommended to allow only SSH protocol version 2 (SSH2) to be used. SSH public SSH Public keys can be added for remote logins with SSHkeys. keys ARG600 Single SIM Variant User Manual...
  • Page 40 Selects the supported dyndns service provider service provider DynDNS client Defines how often (in seconds) the device's IP is checked update interval DynDNS Arctic name reported to service, for example, host name hostname Table continues on next page ARG600 Single SIM Variant User Manual...
  • Page 41 SSH private key to be used if the SSH connection protocol is identity selected. SSH public SSH public key to be used if the SSH connection protocol is selected. This key can be copied to Patrol server. Table continues on next page ARG600 Single SIM Variant User Manual...
  • Page 42 Allow remote Enables remote management by Patrol server No, Yes management Allow LAN Allows periodical local network scan for ABB devices. Currently, No, Yes device scan the supported device is RIO600. ARG600 Single SIM Variant User Manual...
  • Page 43: Section 9 Iec-104 Application Settings

    4800, 9600, 19200, 38400, 57600 Data bits Number of data bits used on IEC-101 serial communication 5, 6, 7, 8 Parity Parity method used on IEC-101 serial communication None, Even, Table continues on next page ARG600 Single SIM Variant User Manual...
  • Page 44 IEC-101 link. The t1 must be longer than the network round-trip-time. The IEC-104 standard suggests 15 seconds. Table continues on next page ARG600 Single SIM Variant User Manual...
  • Page 45 Reply header Defines the timeout in milliseconds that the device waits the 1...65000 timeout reply to start from IEC-101 slave after command or request. Table continues on next page ARG600 Single SIM Variant User Manual...
  • Page 46 0.1 second increments for packet collector. If there has been data on packet collector over MAX TIME, the data is sent to network. The value must be smaller than t1. Table continues on next page ARG600 Single SIM Variant User Manual...
  • Page 47 Other settings Write syslog Write syslog defines if the error messages are stored to system No, Yes log file or not. The system log is available by using Web user interface. ARG600 Single SIM Variant User Manual...
  • Page 49: Section 10 Modbus Application Settings

    Modbus ASCII over TCP and Modbus ASCII over UDP network protocols • Generates and filters out gateway exceptions • Makes automatic connection management • Enables multiple server sessions over the network • Offers unlimited amount of masters on the network side ARG600 Single SIM Variant User Manual...
  • Page 50: Modbus Mode

    “gateway exception message” back to the master if the exception generation is enabled. Otherwise, the reply is returned. Multiple masters can connect simultaneously to the Gateway, which handles the multiplexing between masters. ARG600 Single SIM Variant User Manual...
  • Page 51: Configuring The Network Master To Serial Slaves Mode

    “Even”, an even parity bit is generated and inspected. If set to “Odd”, odd parity bits are generated and inspected. Stop bits Defines the number of stop bits used in Modbus serial 1, 2 communication. Table continues on next page ARG600 Single SIM Variant User Manual...
  • Page 52 If set to “Yes”, gateway exception replies from the slave side are No, Yes exceptions passed to the master. If set to “No”, the replies are filtered away. Network server settings Table continues on next page ARG600 Single SIM Variant User Manual...
  • Page 53 Defines if connection testing is performed by sending TCP No, Yes keepalive keepalive packets at certain intervals. enabled for TCP network communication. If set to “Yes”, testing the TCP connection with slave is enabled. ARG600 Single SIM Variant User Manual...
  • Page 55: Section 11 Troubleshooting

    With these settings, the Internet should be accessible on the laptop. 11.2 Viewing the system log In the left pane, under Tools, select System Log. If necessary, refresh the system log with the Web browser’s reload or refresh button. ARG600 Single SIM Variant User Manual...
  • Page 57: Section 12 Technical Data

    5...85% RH (non condensing) Protection class IP30 Table 21: Supported protocols Master protocol Slave protocol IEC 60870-5-104 IEC 60870-5-101 Modbus TCP Modbus RTU/ASCII TCP/IP, UDP/IP (DNP3) Serial gateway - serial port data stream (such as DNP3) ARG600 Single SIM Variant User Manual...
  • Page 58 IEC 60870-5-101 protocol support Full serial and modem signals 300...460 800 bps Data bits: 7 or 8 Stop bits: 1 or 2 Parity: None, Even, Odd Flow control: None, RTS/CTS Protection: 15 kV ESD and short circuit ARG600 Single SIM Variant User Manual...
  • Page 59 EN 61000-4-4 (2012-04) Surge EN 61000-4-5 (2005-11) Conducted radiofrequency electromagnetic field EN 61000-4-6 (2008-10) Power frequency magnetic field EN 61000-4-8 (2009-09) Table 24: RoHS and REACH compliancy Description Reference Directive RoHS directive 2002/95/EC REACH directive 2006/1907/EC ARG600 Single SIM Variant User Manual...
  • Page 61: Section 13 Glossary

    PLCs and RTU devices. Modbus ASCII Link mode using 7-bit ASCII characters Modbus RTU Link mode using 8-bit binary characters Network time protocol Password authentication protocol Random access memory Ring Indicator RISC Reduced Instruction Set Computer ARG600 Single SIM Variant User Manual...
  • Page 62 SCADA Supervision, control and data acquisition Subscriber identity module SNTP Simple Network Time Protocol Transmission Control Protocol TCP/IP Transmission Control Protocol/Internet Protocol Transmit exchange data User datagram protocol Virtual Private Network Wide area network ARG600 Single SIM Variant User Manual...
  • Page 64 — ABB Distribution Solutions P.O. Box 699 FI-65101 VAASA, Finland Phone +358 10 22 11 abb.com/mediumvoltage © Copyright 2022 ABB. All rights reserved.

Table of Contents