MV100 ELECTRIC CONTROLLERS T100, T200 THERMOSTATIC CONTROLLERS AND V100 RADIATOR VALVES
Connections:
Inlets Available:
Internally threaded.
Sweat (1/2 in. and 3/4 in. only).
Outlets Available:
Union nut with threaded tailpiece.
Sweat (1/2 in. and 3/4 in. only).
Union nut with sweat tailpiece (1/2 in. and 3/4 in. only).
Capacity:
C
(gpm at 1 psi drop across fully-open valve):
v
1/2 in.: 2.5.
3/4 in., 1 in.: 2.7.
Btuh (Btu/hr at 7 psi drop across fully-open valve):
1/2 in.: 59,100.
3/4 in.: 63,800.
1 in.: 70,500.
Accessories:
203225 Replacement Bulb Guard for T100F.
272844 Locking Cap and Limit Pins for T100M.
272873 MT100C Cartridge Tool Driver Upgrade Kit.
A100D Valve Adapter to use T100,T200 on RA2000 valve
bodies (manufactured by Danfoss Inc.).
A100M Valve Adapter to use T100,T200 on TM valve bodies
(manufactured by MACON® Control Corporation).
A104F Limit Pins for T100A,F.
CA100A Replacement Valve Cartridge (plastic body).
CA100B Replacement Valve Cartridge (metal body).
G111B Bulb Guard to protect T100C sensor when wall-
mounted.
MT100L Removal Tool for T100M.
MT100C Valve Cartridge Replacement Tool for system
under pressure.
Q110D Inlet Strainer Inserts for NPT V100 (models
available for 1/2 in. and 3/4 in. valves).
SA123A Steam/Air Vent for V100P One-pipe Steam Valve.
B MAX.
Fig. 3. V100P Dimensions.
NOTE: Refer to Table 3 for detailed valve dimensions for
each valve size.
Valve
V100D
V100E
V100F
V100G
V100P
a
B Max dimension is with T100A control installed, except for
the V100P, for which it is without the steam/air vent installed.

INSTALLATION

When Installing this Product...
A
C
M17016
IMPORTANT
5
Table 3. Valve Dimensions.
Size
A
in in.
in in. (mm)
1/2
3-3/4 (95)
3/4
4-3/16 (106) 4-1/16 (104) —
1
4-1/2 (114)
1/2
2-5/16 (58)
3/4
2-5/8 (66)
1
2-15/16 (74) 4-5/16 (110) 1-5/16 (34)
1/2
2-1/8 (54)
3/4
2-1/2 (64)
1
2-15/16 (74) 5-3/16 (132) 1-7/16 (37)
1/2
2-5/8 (66)
3/4
2-15/16 (74) 4-1/16 (104) —
3/8
1-11/16 (43) 3-13/16 (98) 1-3/16 (31)
1. Read these instructions carefully. Failure to follow them
could damage the product or cause a hazardous
condition.
2. Check the ratings given in the instructions and on the
product to make sure the product is suitable for your
application.
3. Installer must be a trained, experienced service
technician.
4. After installation is complete, check out product
operation as provided in these instructions.
CAUTION
Equipment Damage Hazard.
Excessive force can distort and damage valve.
Do not overtighten the union nut.
CAUTION
Equipment Damage Hazard.
Driving an unmounted MV100 can damage the
actuator beyond repair.
Mount the MV100 before applying power to the
actuator.
CAUTION
Sweat Valve Damage Hazard.
Soldering the valve with the cartridge or controller
attached can damage the device.
Prior to attaching valve to piping, remove controller
and cartridge from potential exposure to heat.
When installing the valve body, ensure that the
arrow (cast into the body) points in the direction of
the flow.
a
B Max
C
in in. (mm)
in in. (mm)
4-1/16 (104) —
4-1/2 (114)
3-13/16 (98) 1 (26)
3-13/16 (98) 1-1/8 (29)
4-1/2 (115)
1-1/8 (28)
5-3/16 (132) 1-3/16 (31)
4-1/16 (104) —
62-3048—1