Emerson Bettis OM9-SCE300 Installation, Operation And Maintenance Manual page 37

Profibus dpv1 interface
Table of Contents

Advertisement

Installation, Operation and Maintenance Manual
VCIOM-17121-EN Rev. 0
Octet 2
Octet 3
Octet 4
Octet 5
Octet 6
11.1.4.2
Identifier Related Diagnosis Block
Octet 7
0
Data Exchange Mode
Bit0
Bit0
Bit0
Bit0
Bit0
Bit0
1
Diag.Pm_Req
Diag.Stat_Diag
DP
Diag.WD_On
Diag.Freeze_Mode
Diag.Sync_Mode
reserved
Diag.Deactivated
reserved
Diag.Ext_Diag_Overflow
Diag_Master_Add
Ident_Number
Ident_Number
Header: SCE300_DPV1 report 0x42
Block_Length
Selection
Section 11: Data Exchange Mode
(1) = Slave has to be re-parameterized
(1) = During start-up phase slave not able
to provide valid diagnosis data
(1) = Fixed at 1
(1) = Threshold monitoring activated
(1) = FREEZE command received
(1) = SYNC command received
(1) = Diagnosis deactivated (sets master)
(1) = Slave has more diagnosis data than fit
into the buffer
Address of the master that has
parameterized the slave 0xFF when slave not
parameterized yet
High byte of the slave's ident number,
SCE300_DPV1 report 0x09
Low byte of the slave's ident number,
SCE300_DPV1 report 0xE3
Low byte of the slave's ident
number, SCE300_DPV1 report 0xE3
Number of octets of this block
including this header
(01) = Identifier
Related Diagnostic
August 2022
33