Store Conditions
• Case is designed to operate at temperatures at either
75°F at 55% relative humidity or 80°F at 55% relative
humidity. Case must be kept in that environment to
ensure case performance and product safety.
• Do not position the case near an HVAC vent.
• Do not position the case near an entrance door. Outside
ambient conditions may have an adverse affect on the
refrigeration performance, a minimum of 15' clearance is
required from doors.
• Do not position the case tight against a ceiling or soffit.
A minimum clearance 10" above the unit is required for
proper compressor discharge air flow.
• Do not block case front panel vent (supplies critical
intake air flow to the compressor)
BEFORE SERVICING
ALWAYS DISCONNECT ELECTRICAL
POWER AT THE MAIN DISCONNECT
WHEN SERVICING OR REPLACING ANY
ELECTRICAL COMPONENT.
This includes (but not limited to) Fans, Heaters
Thermostats, and Lights.
Uncrating the Stand
Place the fixture as close to its permanent position as
possible. Remove the top of the crate. Detach the walls from
each other and remove from the skid. Unbolt the case from
the skid. The fixture can now be lifted off the crate skid. Lift
only at base of stand!

6. Installation

Do Not Install the Vented Panels of the
self-contained model against a wall or
other storage fixture.
Located in the lower front and rear of the self-contained
models are vented panels. These panels allow air circulation
to the condensing unit. Blocking or restricting air circulation
through these panels can cause poor performance and
damage the refrigeration system.
Exterior Loading
These models have not been structurally designed to support
excessive external loading. Do not walk on their tops;
This could cause serious personal injury and damage to
the fixture.
It is the contractor's responsibility to install
case(s) according to local construction and
Levelling
A LEVEL CASE IS NECESSARY TO INSURE
PROPER OPERATION AND WATER DRAINAGE.
Note: To avoid removing concrete flooring, begin
lineup leveling from the highest point of the store
floor.
7
ATTENTION
INSTALLER
health codes.