JUMO EM Series Operating Instructions Manual page 23

Panel-mounting thermostats
Hide thumbs Also See for EM Series:
Table of Contents

Advertisement

Average
(in % from the scale range) referring to the limit value.
ambient tem-
When the ambient temperature on the switch head and / or the capillary devi-
perature
ates from the calibration ambient temperature +22 °C, a switching point offset
influence
occurs.
Higher ambient temperature = lower switching point
Lower ambient temperature = higher switching point
Temperature
For detailed information, please refer to the graphical presentation in data
compensation
sheet 602026
"707"
All manuals and user guides at all-guides.com
For temperatures with scale limit value / limit value:
≥ +200 °C ≤ +350 °C
< +200 °C
7
Ambient temperature influence on the switch head in %/K
0.43
Ambient temperature influence on the capillary in %/m
0.09 · K · m
Ambient temperature influence on the switch head:
Ambient temperature influence on the capillary in K/m
6 Device Description
≥ +400 °C ≤ +500 °C
STW (STB)
Hysteresis in %
7
0.35
0.07 · K · m
STB
0.35 K/K
0.07 K/K·m
10
0.24
0.05 · K · m