Retrofitting An Inductive Limit Switch - Samson 3730-3 Mounting And Operating Instructions

Electropneumatic positioner
Table of Contents

Advertisement

8
Retrofitting an inductive limit
switch
Required retrofit kit:
Limit switch
Order no. 1400-7460
1. Take off the rotary pushbutton (3) and
cap (1), unthread the five fixing screws
(2) and lift off the plastic cover (9).
2. Use a knife to cut an opening at the
marked location (4).
3. Push the connector (11) with cable
through the opening and secure the
proximity switch (7) on the cover with a
dot of glue.
4. Remove the jumper at the socket ST1 of
the top board and insert the cable con-
nector (11).
5. Guide the cable in such a manner that
the plastic cover can be placed back
onto the positioner. Insert the fixing
screws (2) and screw tight. Attach the
clamping plate (8) onto the proximity
switch.
6. Attach the rotary switch (5). Make sure
the flattened side of the positioner shaft
is turned so that the rotary switch (5) can
be attached with the metal tag next to
the proximity switch.
7. Important!
On start-up of the positioner, set the op-
tion "inductive alarm" under Code 38
from NO to YES .
1
Cap
2
Screws
3
Rotary pushbutton
4
Marking
5
Rotary switch
6
Metal tag
7
Proximity switch
8
Clamping plate
9
Plastic cover
11 Connector

Retrofitting an inductive limit switch

Socket ST1(11)
Fig. 20 · Retrofitting an inductive limit switch
1
2
4
3
5
8
7
6
9
7
63
EB 8384-3 EN

Advertisement

Table of Contents
loading

Table of Contents