DOK-INDRV*-KCU01******-IT01-EN-P
Rexroth IndraDrive Mi Electronic Control System KCU01
5.2.4

Connection Point of Equipment Grounding Conductor

WARNING
The devices of the Rexroth IndraDrive Mi product range are devices with in‐
creased leakage current (greater than AC 3.5 mA or DC 10 mA).
Therefore, always install a stationary connection of the equipment grounding
conductor.
In a Rexroth IndraDrive Mi drive system, connect the equipment grounding
conductor connections of all devices and additional components to the equip‐
ment grounding system.
1
Connection point of equipment grounding conductor at supply unit
with connection to equipment grounding system
2
Joint bars connect equipment grounding conductors of neighboring
devices
3
Hybrid cables connect equipment grounding conductors of KSM01/
KMS01 with one another and with equipment grounding conductor of
KCU01
4
Second connection point of equipment grounding conductor
Fig.5-6:
Connection Point of Equipment Grounding Conductor
The connection point of the equipment grounding conductor
shown above applies to distributed drive controllers KMS01, too.
Bosch Rexroth AG
Dangerous contact voltage at device housing!
Lethal electric shock!
35/63