GFPS-9 Supplementary Notification Appliance Circuit Installation Manual
twist two conductors together.
Figure 4-4 Class A Supervised Input/Output Connections
4.5.2

Class B Supervised Wiring

Figure 4-5 shows how to wire for Class B input and output supervision. Use in/out wiring methods for proper
supervision (Refer to the Appendix for notification appliances approved for use with the GFPS-9.)

Class B Output Notification Circuits

Figure 4-5 shows four, 1.5 A devices wired as Class B.
Place a 4.7k ohm EOL resistor (provided) at the end of each circuit to enable supervision when using all outputs
as Class B notification appliance circuits. The 4.7k EOLs must be wired to the terminals whether or not you are
using all output terminals.
4-11